5. INGEREV CITY Wall, INGEREV CITY Ground

5.1. Local communication

INGEREV CITY Wall and INGEREV CITY Ground charging stations have a local RS-485 data bus that
enables interconnection between the stations. Consult the corresponding installation manual for more
information on this subject.

5.2. Remote communication

5.2.1. Remote communication via external modem

1.
Connect the communications card with Ethernet connection to one of the charging stations located at one
end of the installation in order to start the communication ring. It can be connected both with the J15
and J17 connectors, as well as the J16 and J18 connectors.
Remove the end of line jumper from the control card.
2.
Connect the wiring that joins the control card to the communications card (see the light grey cabling in
the following figure).
Connect the modem to the communications card (see the white cable in the figure below).
At the free RJ45 connector, connect the station to the next station on the communication ring (see dark
grey cable in the figure below).
26
Pin
Colour
1
White/Orange
2
Orange
INGEREV CITY Wall, INGEREV CITY Ground
Control card jumper
Signal
RS-485 B (+)
RS-485 A (–)
ABA2017IQM01_A - Installation and Operation Manual