Have work on the electrical part of the pump carried out only by a qualified electrician.
The power supply and control cable is connected at the factory and electrically tested!
Cable removal requires an earth contact and insulation resistance test according
to VDE 0701-0702.
• The electrical connection must be established via a fixed power cable (3 x 1.5 mm
mum cross-section), equipped with a plug and socket connector or an all-pole switch
with a minimum contact opening width of 3 mm.
• The mains connection cable is to be routed into the system's switchbox with a strain relief.
The strain relief and tightness against dripping water/condensation water must be ensured.
The cable is to be provided with a drip loop if necessary.
• The following minimum requirements are to be met if shutdown takes place by means
of an on-site network relay: Rated current ≥ 8 A, rated voltage 250 V AC, contact
materials: AgSnO2 or Ag/Ni 90/10.
• Fuse protection: 10/16 A, slow-blow or automatic fuse with C characteristic.
• A motor protection switch supplied by the customer is not required. Nevertheless, if such
a protection switch is available in the installation, it must be bypassed or set to the highest
possible current.
• It is recommended to safeguard the pump with a residual-current device.
Labelling: residual current type A
When dimensioning the residual-current device, consider the number of pumps con-
nected and their rated motor currents.
• Leakage current per pump I
7.2.1 Configuration of the connection cable
Mains cable (Fig. 1a/b, item 6)
Control cable (Fig. 1a/b, item 7)
Control via analogue signal 0...10 V (2-wire or 4-wire cable)
40
≤ 3.5 mA (in acc. with EN 60335).
eff
The free end of the cable is to be inserted in the system's
switchbox:
• Brown wire:
• Blue wire:
• Green/yellow wire:
• L, N,
1~230 V AC, 50/60 Hz, DIN IEC 60038
• Earth the pump/installation as per regulations.
• Wire 1 (brown):
• Wire 2 (white(blue)): 0...10 V (signal)
• Wire 3 (blue):
• Wire 4 (black):
0-10V
SSM
or type B
.
L1 (phase)
N (neutral conductor)
(protective earth)
: Mains supply voltage:
GND (signal earth)
SSM (if present)
SSM (if present)
2
mini-
WILO SE 12/2017