4.5

Fitting the lamps

Only use LED tubes that have been certified for these light
fittings, see Technical data and type label!
The LED tubes (G5) is to be inserted to its stop into the marked holders
so that both pins on either side of the lamp engage in the holder. Only the
holders on this side are wired with connecting wires.
Insert the cable entries of the LED - tubes into the socket use it in an
opposite side.
The lamp is to be inserted to its stop into both holders, so that both pins
on either side of the lamp engage in the holder.
Then turn the lamp to its lock-in position, see fig. 8 and fig. 9.
If the LED tubes are inserted with swapped ends, there is no function.
Observe the emission direction of the LED tubes.
Attention! Lamp exchange must be carried out while energy is
switched off.
Option: automatic double-pole switch while opening the protective
bowl.
5.

Taking into operation

– Prior to operation, check the light fitting for its proper functioning and
installation in compliance with these operating instructions and other
applicable regulations!
– Only carry out insulation measurements between PE and the external
conductor L1(L,L2,L3) as well as between PE and N!
– measuring voltage: max. 1 kV AC/DC
– measuring current: max. 10 mA
– The lamp may only be operated in the closed state.
Explosion protected light fittings
Series: nLL* 15 LED 600/1200/1200HT/1500
6.
Observe the national regulations applicable to the maintenance,
servicing and test of electrical apparatus as well as the general rules
of engineering (e.g. IEC/EN 60079-17)!
Servicing
When servicing, in particular those components that affect the type of
protection, will have to be checked, e. g.:
– Housing and protective bowl for any cracks or damages.
– Gaskets for their perfect condition.
– Terminals and blanking plugs for their firm fit.
– Because of the risk of an electrostatic charge, the light fitting shall only
be cleaned with a damp cloth or sponge!
Only use customary household washing-up liquid diluted in water as
specified! The water temperature may be max. 50ºC. After that, rinse
with clear water to prevent the risk of tension cracks in the protective
bowl!
– Lamp replacement: Keep replacement intervals as specified by the lamp
manufacturer!
7.
Prior to replacing or removing any components, observe the following:
Cut the apparatus off the voltage before opening it or carrying
out repairs!
Only use certified genuine CCH/CEAG spare parts! (See CCH/CEAG spare
parts list).
Subject to alteration or supplement of this product series.
Regarding waste disposal, observe the relevant national regulations!
All components are marked with relevant material signs.
Maintenance
Repair
GB
9

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Led 600Led 1200Led 1200htLed 1500

Table des Matières