Dimensions in mm
GHG 411 81
GHG 411 82
GHG 411 83
GHG 412 82
Flange opening for GHG 412 82
X = fixing dimensions
10
Explosion-protected control units
GHG 411 and 412
1
Technical data
1.1
Control unit assemblies
ATEX type examination certificate:
Marking acc. to 2014/34/EU and standard:
EN 60079-0
IECEx type examination certificate:
Category of application:
IEC60079-0
Rated voltage:
Rated current:
Permissible ambient temperature:
Other temperatures possible for special versions.
Perm. storage temperature in original packing:
Degree of protection to IEC/EN 60529:
Insulation class acc. to IEC/EN 61140:
PE- terminal:
Terminals:
Cable entries (standard version):
suitable cables and test torques of the pressure srew
Cabel entry:
seel 1+2+3
min.
1 2
3
(Ø mm / Nm)
max.
seel 1+2
min.
1 2
3
(Ø mm / Nm)
max.
seel 1
min.
1 2
3
(Ø mm / Nm)
max.
Test torque for screw in thread cable entry (Nm)
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 + 3 for the intermediate region.
(2)
When selecting the seal rubber, ensure that the cap nut can be tightened when carrying out any future
maintenance work on the cable entry.
Weight:
Control unit GHG 411 81 (P411)
Control unit GHG 411 82 (P412)
Control unit GHG 411 83 (P413)
Control unit GHG 412 82 (F412)
Test torques: Cover screws
1.2
Actuator general
ATEX type examination certificate:
Marking acc. to 2014/34/EU and standard:
EN 60079-0
IECEx type examination certificate:
Category of application:
IEC60079-0
Operating temperature:
PTB 00 ATEX 3117
D II 2 G Ex e mb IIC T6 Gb
D II 2 G Ex e ib mb IIC T6 Gb
D II 2 G Ex d e mb IIC T6 Gb
D II 2 G Ex d e ib mb IIC T6 Gb
D II 2 D Ex tb IIIC T80 °C Db
IECEx BKI 04.0003
Ex e IIC T6
Ex e ib IIC T6
Ex d e IIC T6
Ex d e ib IIC T6
up to max. 690 V
max. 16 A
-20° C to +40° C (standard version)
-20° C to +40° C
IP 66 (standard version)
IP 65 Double push button
I - with metal flange
II - plastic terminal boxes fulfil this requirement
2 x 4 mm²
see built-in components
1 x M25
M12
M16
---
---
(1) (2)
5,5 / 1,0
---
(1) (2)
7,0 / 1,0
5,0 / 0,8
7,0 / 1,0
(2)
7,0 / 1,0
10,0 / 1,4
1.2
3.3
approx. 0.25 kg (empty weight)
approx. 0.35 kg (empty weight)
approx. 0.45 kg (empty weight)
approx. 0.80 kg (incl. measuring instrument)
2.50 Nm
IBExU14ATEX1030U
D II 2 G Ex d e IIC/IIB Gb
D I M 2 Ex d e I Mb
IECEx IBE 14.0005U
Ex d e IIC/IIB Gb
Ex d e I Mb
-45 °C
to
II 2 G ... IIC
-60 °C
to
II 2 G ... IIB
E
M20
M25
M32
5,5 / 1,5
8,0 / 1,5
---
7,0 / 1,0
10,0 / 2,0
7,0 / 1,5
10,0 / 2,3
14,0 / 3,0
9,0 / 1,4
13,0 / 2,6
17,0 / 4,0
9,5 / 1,0
13,5 / 1,3
17,5 / 1,5
13,0 / 1,7
17,5 /2,3
21,0 / 1,3
2.7
3.0
5.0
+80 °C
+80 °C