RESUME DE LA SEQUENCE DE TESTS (Suite)
ETAPE ACTION EXECUTEE
9
TESTER POMPE EAU, REGULATEUR
UDC, CONTROLE CONDUCTIVITE
ET VANNE MODULANTE
(+) DROIT:
CENTRE:
(-) GAUCHE: FERME VANNE
10
TESTER MOTEUR VANNE
CARBURANT ET REGLAGE FDC
DEBIT RALENTI ET TRINGLERIE
(+) DROIT:
CENTRE
(-) GAUCHE: FERME VANNE
11
DEMARRER POMPE CARBURANT,
PURGER CARBURANT ET REGLER
PRESSOSTATS OLP ET OHP
(l) DEM.:
(O)ARRET:
(+) DROIT:
CENTRE
(-) GAUCHE: FERME VANNE CARB.
12
TESTER ET REGLER PRESSION AIR
REGULATEUR APR ET PRESSOSTAT
AAP
(+) DROIT:
(-) GAUCHE: FERME VANNE AAV
13
TESTER VENT. COMBUSTION
REGLER PRESSOSTAT AIR COMB.
(+) DROIT:
(-)GAUCHE: ARRETE VENT.
14
TESTER TRANSFO ALLUMAGE
(+) DROIT:
VOYANT FLAMME DOIR RESTER
ETEINT
15
ESSAI D'ALLUMAGE
* 10 SEC SANS FLAMME
"RESET" POUR ALLER A L'ETAPE 0
© SAMUEL JACKSON, INCORPORATED 2003 ALL RIGHTS RESERVED – TOUS DROITS RESERVES
HUMIDAIRE HU-60-1265
(POUR LA VERSION LOGICIELLE 1.0)
OUVRE VANNE
MAINTIENT POSITION
OUVRE VANNE
MAINTIENT POSITION
OUVRE VANNE FOV
FERME VANNE FOV
OUVRE VANNE CARB.
MAINTIENT POSITION
OUVRE VANNE AAV
DEMARRE VENT.
IGT SOUS TENSION
PAGE 55 de 89 HUMIDAIRE A PETROLE HU-60-1265
CONDITION POUR ETAPE
SUIVANTE
"RESET" ET DEBIT D'AIR OK
"RESET" ET DEBIT D'AIR OK
"RESET" ET DEBIT D'AIR OK
"RESET" ET DEBIT D'AIR OK
"RESET" ET DEBIT D'AIR OK
"RESET" ET ABSENCE SIGNAL FLAMME
(10 SEC)
FLAMME CONDUIT A 16