Lamp Replacement; Repair / Overhaul / Modifications; Testing Restricted Breathing Properties; Disposal/Recycling - Cooper Crouse-Hinds NVMV Série Instructions D'installation Et De Maintenance

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

conditions and the hours of operation. The recommendations given
within IEC/EN60079-17 for recurring checks must be observed. If the
luminaire is opened for maintenance purposes or to replace the lamp,
ensure that the "nR" properties are not affected.
This could be done by testing the restricted breathing properties as
per Section 10.

8.3 LAMP REPLACEMENT

The suggested interval between lamp changes given by the lamp
manufacturer must be followed (see Section 6.7 for details).
After replacing the lamp, ensure that the "nR" properties have not
been affected. This could be done by testing the restricted breathing
properties as per Section 10, for example.
9.0 REPAIR/OVERHAUL/MODIFICATIONS
Repairs and overhaul may only be carried out with genuine Cooper
Crouse-Hinds spare parts.
Before replacing or disassembling individual parts, observe the
following:
Disconnect the power supply to the equipment before
maintenance/repair.
Make sure that there is no explosive atmosphere when opening the
equipment.
Only use original spare parts.
If the luminaire was previously in operation, wait 10 minutes before
opening.
Repairs that affect the explosion protection may only be carried out by
Cooper Crouse-Hinds or a qualified electrician in compliance with the
applicable national rules.
Figure 13 - Restricted Breathing
Test port lable (Test point can be
found on cover marked by label)
Pa
300
A
150
0
0
80
= ACCEPTABLE RANGE
A
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness
thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should
determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
s
Cooper Industries Inc.
Crouse-Hinds Division
Copyright © 2009, Cooper Industries, Inc.
Modifications to the device or changes to its design are not permitted.
After carrying out repair or overhaul work, ensure that the "nR"
properties have not been affected.
This could be done by testing the restricted breathing properties as
per Section 10, for example.

10.0 TESTING RESTRICTED BREATHING PROPERTIES

All screw plugs and cable glands must be correctly tightened.
Over-tightening the screw elements can destroy the thread.
Connect the testing equipment to the test port on the luminaire (see
Figure 13).
Use the values specified in IEC60079-15 for the test.

11.0 DISPOSAL/RECYCLING

When the apparatus is disposed of, the respective national regulations
on waste disposal must be observed.
Figure 14 - Wiring Diagram for High Pressure (HPS)
and Metal Halide (MH) 70, 100, 150, 250 W
IF 1599
Revision 1
New 07/09

Publicité

Table des Matières
loading

Table des Matières