Terminal clamp 2 is the joint reference point (-) for both alarm zones. Connect the
sensors with N.C. contacts in sequence, and those with N.O. contacts in parallel
If no sensors with N.C contacts are used, a 10kOhm resistor (EOL) must be inte-
grated for connection (included in the delivery).
Alarm zone 2 is best suitable for sensors that are installed in the
inside area (such as motion detectors), since these sensors would
trigger alarm when the house is entered. An alarm is only triggered
after the end of the activation delay (= 30 seconds). The alarm system
can be disarmed in this period (for this, the mode selection switch at
the front must be returned to the "OFF" position).
To ensure proper sensor operation with an N.C. contact it must be
ensured that every sensor with an N.C.contact has a maximum resis-
tance of 1kOhm.

7.2 External signalling device connection

A maximum of two 8 Ohm signalling devices / speakers can be connected in
parallel to the terminal clamps 4 (-) and 5 (+).
1
2
3
HORNS
4
5
6
7
8
8
8
9
10
11
12
37