Gas burner control LME 21
Operation, display, diagnoses
Burner control has initiated lockout
 Red signal lamp illuminated
Burner control in operation
 Green flame signal lamp illuminated
FS
Diagnosis of cause of fault
FS
Blinkccode
2 x blinks
••
3 x blinks
•••
4 x blinks
••••
5 x blinks •••••
7 x blinks
•••••••
8...9 x blinks
•••••••••••••••••
10 x blinks
••••••••••••••••••
During the time the cause of fault is diagnosed, the control outputs are deactivated.
- The burner remains shut down
- Expection: Error message «AL» at terminal 10
The burner is switched on only after a reset is made
- Press lockout reset button 0,5...3 s
AL
After lockout, the red signal lamp is steady on.
Steady on
For reading the cause of fault, refer to the blink code given in the following table:
AL
Illuminated phase
(waiting time
Possibleccause
• No establishment of flame at the end of «TSA»
• Air pressure switch does not close
• Air pressure
• Time monitoring air pressure switch
• Loss of flame during operation
• free
• Internal error
Reset
Press lockout reset button for 0,5...3 s
Diagnosis of cause of faul
– Wait > 10 s
– Press lockout reset button for > 3 s
– Read blink code of red signal lamp
 «Error code table»
Restart
Press lockout reset button for 0,5...3 s
Press lockout reset button
> 3 s
10 s)
d
Störung
Error code table
- Fault or soiled ionization elektrode
- Faulty or soiled fuel valves
- Poor adjustment burner
- Faulty ignition device
- «LP» faulty
- «LP» incorrectly adjusted
- Fan motor does not run
- «LP» faulty
- «LP» incorrectly adjusted
- «LP» faulty
- Poor adjustment burner
- Faulty or soiled fuel valves
- Short-circuit between ionization probe
and ground
- Wiring error
- Faulty output contact
- Other errors
Blink code
Off
Blink code
ca. 3 s
23