10.6
Connect gas supply, check the gas connection pressure
Clamping cam (gas regulator)
Remove the
screws
Hose
Pressure gauge
. Read the gas connection pressure.
− If the pressure is too high: Install a pressure limiter.
− If the pressure is too low: Check the house installation / inform the gas supply company.
− Do not set and start up the appliance, if the gas-primary pressures have been exceeded or
fallen short of!
After connection and pressure check
. Close the connection nipple with the screw plug.
. Check all gas-bearing parts for tightness (leak spray).
. Closing front panel.
. Connect the clamping cam.
. Install washer and lever for gas tap and secure using threaded pin.
Threaded pin
Washer
Lever
Undo screws
Screwdriver
Connection nipple
Gas tap
Gas connection
Remove front panel
Front panels must only be removed by authorized
customer service or gas fitter!
. Undo threaded pin and pull off lever.
. Remove the clamping cam.
. Release the screws below the front panel.
● The number of screws depends on the width of
the appliance.
. Remove the top screws.
Connect gas supply
● Do not route the gas supply line along hot sur­
faces or sharp edges.
. Connect gas supply.
. Connect the appliance to the equipotential
bonding system.
. Check all gas-bearing parts for tightness (leak
spray).
Check the gas connection pressure
. Close the gas tap.
. Loosen the screw plug in the connection nipple
with a screwdriver.
. Connect the gauge to the connection nipple.
. Open the gas tap at the building and on the
device.
. Ignite the gas burner.
. Check that the main flame is burning.