Safety instructions

The control units GHG 418 .. are
not suited for use in Zone 0.
The operations must be carried
out by electrical suitably trained in hazardous
area with knowledge of increased safty
explosion protection IEC/EN 60079-14.
The temperature class and type of protection
stated on the apparatus shall be observed.
Modifications or changes to the control units
are not permitted.
They shall be used for their intended purpose
and shall be in a perfect and clean state.
Prior to being put into operation, the control
units shall be checked in accordance with the
instructions as per section 6.
Before initial operation, any foreign matter
shall be removed from the apparatus.
Apparatus without a protective cap may only
be built into approved or certified enclosures,
operating panels or switch cabinets.
The national safety rules and regulations for
the prevention of accidents, as well as the
safety instructions included in these
operating instructions, that, like this text, are
set in italics, shall be observed!
3

Conformity with standards

The apparatus have been designed, manufac-
tured and tested according to the state of the art
and to DIN EN ISO 9001:2015 and
IEC 80079-34:2011.
The apparatus is conform to the standards
specified in the EC-Declaration of conformity,
enclosed separately.
6
Explosion-protected control units GHG 418
1

Technical data

1.1 Control unit assemblies with protective cap
ATEX type examination certificate:
Marking acc. to 2014/34/EU and standard:
EN 60079-0
Rated voltage:
Rated current:
Ambient temperature range:
(Special versions permit deviating temperature ranges)
Perm.storage temperature in original packing:
Degree of protection to EN/IEC 60529:
Insulation class acc. to EN/IEC 61140:
Weight:
protctive cap
Cable entry:
Gewicht:
Schutzkappe
Test torques:
Terminal:
Cap nut of the plastic cable entry
Self cutting screw (strain relief)

1.2 Pushbutton and switch

EC type examination certificate:
EC type examination certificate:
Rated voltage:
Rated current:
Switching capacity acc. to AC 15:
Switching capacity acc. to DC 13:
with L/R relation of :
with gold-tipped contacts:
Supply terminal:
Weight:
4

Field of application

The control units are intended for use in
potentially explosive atmospheres in zones 1,2 in
accordance with IEC/EN 60079-10-1.
The enclosure materials used, including any
external metal parts, are high quality materials
that ensure a corrosion resistance and resistance
to chemical substances according to the
requirements for use in a "normal industrial
atmosphere":
- impact resistant polyamide
When used in extremely aggressive atmos-
pheres, the additional data relating to the
chemical resistance of the plastics being used
shall be taken from the data sheet
GHG 902 4001 P0001.
PTB 99 ATEX 1034
D II 2 G Ex d e IIC T6
up to max.500 V
max. 16 A
-20 °C to +40 °C
-20 °C to +40 °C
IP 66 (with protective cap)
I - the apparatus fulfil this requirement
2 x 4 mm²
see built-in components
(Ø 7 - 15 mm)
approx. 0.05 kg
2,50 Nm
3,50 Nm
2,00 Nm
D II 2 G Ex d e IIC/IIB Gb
D I M2 Ex d e I Mb
IBExU14ATEX1030U
up to max.500 V
16 A
250 V / 6 A
500 V / 4,0 A
24V/6 A L/R 30ms;
60V/1,0A L/R 30ms
110V/1,0A L/R 30ms; 220V/1,0A L/R 15ms
max. 400 mA
2 x 1,0 - 2,5mm²
approx. 0,15 kg
5
Application / Properties
The control units GHG 418 .. are intended for the
local control of electrical installations in
potentially explosive atmospheres. These
apparatus components are built into switch
cabinets, operating panels or machinery
according to the individual requirements.
The version with gold-tipped contacts is suited
for switching extra-low voltage circuits. Special
attention shall be paid to the maximum current
load (see technical data, page 6). The contact
chamber of the gold-tipped version is marked
with the letter "G" or colour-coded.
To ensure a safe and reliable disconnection, the
normally closed contacts are designed as
compulsory opening contacts.
GB