As in indication, it should be kept in mind that the field
of variation in output obtainable with good combustion
is from 1 to 1/3 of the maximum output given on the
rating plate.
!
The air pressure switch must be set when the
burner is started up and must be in function with
the pressure value verified during operations with
the ignition flame; otherwise the control box will
go to "shut down".
DIAGRAM OF LIGHT OIL MODULATING BURNERS ( MAGNET - NOZZLE WITHOUT PIN)
CONNECTION AT THE FUEL
FEEDING DIAGRAM FOR
ONE OR MORE BURNERS
(SEE 0002901120)
1
FILTER
2
BURNER PUMP
3
PRESSURE GAUGE 0 - 40 BAR
4
ATOMIZER UNIT
5
RETURN NOZZLE WITHOUT PIN
6
ROD WITH CLOSING PINS
7
BY-PASS HOLES
8
CLOUSING SPRING
9
OPENING ELECTROMAGNET
10 RETURN PRESSURE REGULATOR
11
MODULATION SERVOMOTOR
12 CONTROL DISK FOR VARIATION OF FUEL / AIR DELIERY
13 AIR REGULATION SHUTTERS
14 FLEXIBLE PIPE
13 / 30
0006080115_200909
E
N
G
L
I
S
H
MIN = 10-12 BAR
MAX = 18-20 BAR