External view
The hanging bolt pitch on horizontal direction (B) is not halved at center with the ceiling opening size.
Therefore, check the relational position in the following figure.
Main unit dimension A
Hanging bolt pitch B
J = M x K
• Dimension
A
RAV-SM560BT-E
700
RAV-SM800BT-E
1000
1. Hanging down of indoor unit
Refer to installation figures of hanging material
and hanging bolt.
• Adjustment of hanging bolt length and nut
position
Adjust hanging bolt length and nut position as
shown in the figure before hanging down the
indoor unit.
Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an installation
place and determine piping direction.
• If the ceiling has been already set, prepare refrigerant pipe, drain pipe, connecting wire, switch panel cord, etc. at
the place where pipe and wire are connected before hanging the main unit.
REQUIREMENT
Hanging bolt
H
4-M10 screw
(Arranged
locally)
Refrigerant pipe
connecting port
(Gas side ØF)
Refrigerant pipe
connecting port
(Liquid side ØG)
Drain pipe connecting port
For vinyl chloride pipe
(Inner dia. 32,
Nominal dia. 25)
B
F
G
H
750
12.7
6.4
252
1050
15.9
9.5
252
75
Main unit dimension 800
Hanging bolt pitch 565
25
2-Ø26 power supply,
pull-out port of remote
controller cord
J
K
M
N
280
280
1
2
580
290
2
3
Hanging bolt
15 to 20
20 to 30
NOTE :
Be sure to set the indoor unit horizontally so as not to
cause malfunction of the float switch or leakage of water.
6
210
720
630
Suction port
(with air filter)
Ø125 knockout hole
450
(Rear face)
Ceiling opening
dimension
470
Check panel
Nut with flange
(or washer and nut)
Square washer
Hexagonal nut