5.3. Electrical connection
The electrical connection must be made by a
qualified electrician and comply with applicable
local standards.
Complete electrical information about the circulator is
given on the data plate.
Power supply network
Use a three-conductor cable (3 x 1,5 mm2 H05 VVF) to
connect mains power to the corresponding terminals
of the circulator: phase (L), neutral (N), and earth ( )
(see FIG. 4).
The power cable must not touch the pipe or the
pump; make sure that it is away from any
moisture.
Check line protection and the mains voltage and
frequency.
The circulator must be connected to the mains via a
switch with an opening distance, on each pole, of at
least 3 mm.
The power outlet must have an earthing contact.
The motor need a protection by contactor /
discontactor.
After making the electrical connections, put the motor
housing.
6. STARTING UP
6.1. Filling, degassing
Never operate the circulator WITHOUT WATER.
- Open the valves on both sides of the circulator and
completely fill the loop.
- Bleed the circuit at the high point.
- Power up the motor to start the circulator.
Risk of burning. In operation, the motor
ATTENTION !
casing may be hotter than 60°C.
7. SERVICING
The circulator needs no special servicing in operation.
8. OPERATING TROUBLE
CAUSES AND REMEDIES
Switch the circulator OFF before doing
ATTENTION !
any work on it.
8.1. THE CIRCULATOR IS NOISY
a) The suction pressure is too low :
- Raise the pressure in the circuit.
b) Foreign bodies in impeller or in the re-flowing
orifice and the pump casing :
- Remove the motor and clean the impeller and the
pump casing.
8.2. THE CIRCULATOR FAILS TO START
a) No power supply to circulator :
- Check that the motor is connected.
- Check the fuses of the installation.
b) Foreign bodies in impeller :
- Remove the motor and clean the impeller.