4.3
USING RIGID VENT COMPONENTS
The vent system must be supported approximately every 3 feet (0.9m) for both vertical and horizontal runs.
Use Wolf Steel Ltd. support ring assembly or equivalent noncombustible strapping to maintain the minimum
clearance to combustibles for both vertical and horizontal runs.
All inner exhaust and outer intake vent pipe joints may be sealed using either red high temperature silicone
sealant W573-0002 (not supplied) or black high temperature sealant W573-0007 Mill Pac (not supplied) with
the exception of the appliance exhaust fl ue collar which must be sealed using Mill Pac.
4.3.1 HORIZONTAL AIR TERMINAL INSTALLATION
Move the appliance into position. Measure the
A.
vent length required between terminal and
appliance taking into account the additional
length needed for the fi nished wall surface
and any 1¼" (31.8mm) overlaps between
venting components.
Apply high temperature sealant W573-0007 (not
B.
supplied) to the outer edge of the inner exhaust fl ue
collar of the appliance. Attach the fi rst inner rigid
pipe component and secure using 3 self tapping
screws. Repeat using the outer rigid pipe.
Insert the vent pipes through the fi restop maintaining the required clearance to combustibles. Holding
C.
the air terminal (lettering in an upright, readable position), secure to the exterior wall and make
weather tight by sealing with caulking (not supplied).
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the
depth of the return fl ange.
4.3.2 EXTENDED HORIZONTAL AIR TERMINAL INSTALLATION
A. Follow the instructions for "HORIZONTAL AIR TERMINAL INSTALLATIONS" section.
Continue adding components alternating inner rigid pipe and outer rigid pipe. Ensure
B.
that all inner rigid pipe and elbows have sufficient vent spacers attached and each
component is sealed and securely fastened to the one prior. Attach the inner telescopic
sleeve to the vent run. Repeat using the outer telescopic sleeve. Seal and secure as
before. To facilitate completion, attach inner and outer couplers to the air terminal.
C. Install the air terminal. See "HORIZONTAL AIR TERMINAL INSTALLATION" section.
All manuals and user guides at all-guides.com
#10x2"
SCREWS
CAULKING
OUTER
RIGID
PIPE
AIR TERMINAL
25.1A
1" (25.4mm)
OVERLAP
HI-TEMP
INNER
SEALANT
RIGID
PIPE
#8x1/2"
SELF DRILLING
SCREWS
26.1A
TELESCOPIC
SLEEVE
20" (508mm)
VENTING
48.1A
W415-1347 / A / 03.19.15
23