Installation instructions
Cover Opening Alarm and External Alarm Input
CAUTION: Cover Opening(Sabotage) Alarm and External Alarm
Input are electrically tied together internally. Alarm contact types,
N.O or N.C are selectable by the Alarm Input Selection Jumper
and the selection types should be matched with Alarm Type in
setup menu.
When both of Cover Opening Alarm and External Alarm Input
are used at the same time, the alarm contact types must match.
Otherwise, alarm malfunctions. When External Alarm Input only
is used with disabling Cover Opening Alarm, remove the jumper
cap of Alarm Input Selection Jumper.
N.O : Alarm is generated when Junction box is OPEN.
N.C : Alarm is generated when Junction box is CLOSED.
Default setting for Alarm Input selection jumper is N.C. It prevents from Alarm is generat-
ing when Junction box is OPEN during installation. Alarm Input selection jumper should
be set to N.O and Event Trigger/Action should be dened to enable Cover opening alarm.
[N.O]
For Cover Opening Alarm, please go to SETUP> Event Rules> Event Processing>
Add Event Trigger should be set to "Alarm In" and then Event Action should be
set as available options
Cover opening alarm switch
(Sabotage alarm)
Alarm Input selection jumper
[N.C]