CONFIGURATION LEVEL

In the Configuration Level, the indicator can be matched to the measurement task by
means of a 12-digit Configuration Code.The Code is displayed in three 4-digit Configu-
ration Words Con1, Con2 and Con3 (display alternates between symbol and value):
Structure of Configuration Word 1 (Con1
ä
Input circuit
Display monitoring
0
°C
Upscale
1
°C
Downscale
2
°F
Upscale
3
°F
Downscale
Input signal / Measurement value for:
Thermocouple
Type
Range [°C]
0
L
-100...900°C
1 J
-100...1200°C
2
K
-100...1370 °C
3
N
-100...1300 °C
4
S
0...1760 °C
5
R
0...1760 °C
6
T
-100...400°C
7 W
0...2315°C
8
E
-100... 1000°C
9
B
0... 1820°C
Ü Only with resistive sensors
* NO = Normally open: relay is energized on alarm
NC = Normally closed: relay is de-energized on alarm and opens the contact.
Ö Measured values below 400°C are outside the specified accuracy!
ä Only relevant for thermocouples and Pt 100.
# If measurement is below -99,9 °C, the decimal point must be adjusted to dP = 0.
< Always acts on LED for L1, also if the "Relay" option is not fitted.
g
Example for the adjustment of Configuration Word Con1: 0200 :
0200 means: Display in °C, input circuit monitor acts upscale / Pt 100 in 3-wire connection, range =
-200...650 / Relay is de-energized on sensor break, no measurement value alarm!
+ If the type of input signal is re-configured, all range-dependent parameters must be
matched to the new measurement range! ( r Deleting; page 12)
6
Con1
Con1):
Con1
Pressing keys I and D changes the value of Con1 (the
longer, the faster). Pressing M stores the setting and Con2 is
displayed.
Sensor type
0 Thermocouple int. CJC
1 Thermocouple ext. CJC
2 Pt 100
3 Resistive sensor
4 Potentiom. transducer
5 Voltage
6 Current
>
Pt 100 #
[°C]
3-wire -200...650
4-wire -200 ...650
Ö
Sensor Input
break
0
1
2
3
4
5
Current
Pot. transducer
[mA]
Resistance [
-1...7,30 0 3-wire 0...400,0
-3...22,00 1 3-wire 0...1500
0...50,00 2 4-wire 0
3 4-wire 0...1500
4
5
6
7
8
9
.
 Alarm 1 <
Operating
principle
value alarm
f
-
-
f
f
f
f
-
f
-
f
f
Voltage
]
[V]
[
-3,00...23,00mV
[
-11,0...69,0mV
[
0,0...160,0 mV
400,
Ü
...
0
[
-0,600...4,400V
Ü
[
-2,00...13,00V
0,00...30,00V
9499-040-47801
*
NC
NC
NC
NO
NO
NO