MOUNTING
The instrument is intended for panel mounting.
EARTH TERMINAL (for grounding interferences)
If outside interference voltage act on the instrument, functional troubles may be caused (concerns also high-
frequency interferences). For grounding interferences and ensuring the electromagnetic immunity, an
earth must be connected: Terminals 7 and A must be connected to earth potential by means of a short
cable (approx. 20 cm. e.g. to switch cabinet ground)! Keep this cable separate from mains cables.
ELECTRICAL CONNECTIONS
Keep mains cables separate from signal and measuring cables. We recommend twisted and
screened measuring cables (screen connected to earth). Protective earth must be connected!
Connected final elements must be equipped with RC protective circuits to contactor manufacturer
specification, this avoids voltage peaks which can cause trouble to the indicator.
The instruments must be protected by an individual or common fuse for a max. power consuption of 10 VA
per unit ( standard fuse ratings, min. 1A) !
Signal and measurement circuits may carry max. 50 V r,m,s, against ground,
a
mains circuits may carry max. 250V r.m.s. between terminals.
2
Standard configuration Con1:0200;Con2:0000; Con3:3000;
Configuration to specification (when ordering)
Digital 280 with 2-wire transmitter supply
Digital 280 with relay outputs 1/2 and 2-wire transmitter supply
Digital 280 with relay outputs 1/2 and RS 422/485 interface
Digital 280 with current output and relay output 2
Digital 280 with current output and relay output 1/2
red LED display
green LED display
red LED display + software options
green LED display + software options
115/230V AC (-15... +10 %)
24 V UC (19 ... 30V= ; -15%..+10% 24V~ )
Con4
:
0000
9499-040-47801