PARAMETER LEVEL
The indicator is matched to the measurement task in the Parameter Level. Only those
parameters are displayed, which are required for the configured indicator:
+ Pressing keys I or D changes the value (the longer, the faster).
The new value is activated after 2 seconds, or by pressing key M briefly; pressing
M also changes to the next parameter.
Parameter symbol and value are displayed alternately.
+ The Parameter Level is exited after a time-out of 30 s, or if key M is pressed
briefly after setting the last parameter.
Parameter name
Lower limit contact 1/2 <
Upper limit contact 1/2 <
Alarm hysteresis 1/2 <
Alarm delay 1/2 #<
Scaling the input signal for display (Only with Con2 = x1xx; r Examples)
1st inputs value for scaling
1st output value for scaling
2nd input value for scaling
2nd output value for scaling
Scaling the display for output signal y
Output span start (0/4mA)
Output span end (20 mA)
Filter time constant (r Hints)
Filter bandwidth ( r Fig. 1)
external CJC (with thermocouples ä)
Ü Display in engineering units of indicator, decimal point is defined by "dP"(r Config.)
* Display in engineering units of measured value, potentiometric transducers in %
Ö This function can be disabled: Press key D until '----' is displayed.
ä only if Con1 = x1xx
# Alarm delay; alarms shorter than the adjusted time are ignored.
< Only if measured value alarm has been configured in Con1 or Con3.
> The following symbols apply analogously for Alarm 2: L_L2; L_H2; HYS2; dEL2
y only possible on version with output current option
+ Pressing key M longer than 5 seconds changes over to the Configuration Level.
8
Symbol Adjustment range of the values
L_L1
>
-999...9999
L_H1
>
-999...9999
HYS1
>
0...9999
dEL1
>
0...9999 s
In 1
-999...< In 2
Ou 1
-999...9999
In 2
> In 1 ...9992 *
Ou 2
-999...9999
( r Examples)
OutL
-999...9999 except OutH Ü
OutH
-999...9999 except OutL Ü
t_F
0,0...999,9 s
b_F
0...9999 Ü
tc_E
0...60 °C (32...140°F)
ÜÖ
ÜÖ
Ü
*
Ü
Ü