APPLIANCE INSTALLATION INSTRUCTIONS.
To limit the heating of the house walls and floor around the fireplace to 65K (K = degrees Celsius above room temperature), and for the
appliance to operate properly, the provisions illustrated in the diagram below should be followed.
Respect the minimum embedding and convection air circuit dimensions (size of the intake for the "air to be heated" and "hot air" outlet
size).
The indicated minimum embedding dimensions guarantee access to operating controls, sufficient space for the moving parts, access and
removal of parts that may need to be replaced.
Hot air outlet size:
24 dm²
30 mm
Fresh air intake size:
8 dm²
50 mm thick rock wool, max conductivity 0.04W/m°C
with aluminium side on the hearth side
concrete
fireplace walls and floor
XD, 31/01/2020
Fireplace 700 ECO
Hood back draught flap min height
500 mm
80 mm
80 mm
Reference: P600672
30 mm
20 mm
Page 3 of 8