Modbus
Register
adress
30011
ROTATIONAL_SWITCH_S4
30012
MOTOR_STATUS
30014
YEAR
30015
MONTH
30016
DAY
30017
HOUR
30018
MINUTE
30019
SECOND
30021
MOTOR_ALARM_COUNT
30022
AN1_ALARM_COUNT
30023
AN2_ALARM_COUNT
30024
AN3_ALARM_COUNT
30025
MINUTES_ON
30026
DAYS_ON
30027
MINUTES_RUNNING
30028
DAYS_RUNNING
30029
P_ALARM_1
30030
P_YEAR_ALARM_1
30031
P_MONTH_ALARM_1
30032
P_DAY_ALARM_1
30033
P_HOUR_ALARM_1
30034
P_MINUTES_ALARM_1
30035
P_SECONDS_ALARM_1
30036
P_ALARM_2
30037
P_YEAR_ALARM_2
30038
P_MONTH_ALARM_2
30039
P_DAY_ALARM_2
30040
P_HOUR_ALARM_2
30041
P_MINUTES_ALARM_2
30042
P_SECONDS_ALARM_2
30043
S_ALARM_1
Data type
Range
Description
0: MIN-MAX mode
1: COP or CAV mode with a 20% setpoint of the full scale
2: COP or CAV mode with a 30% setpoint of the full scale
3: COP or CAV mode with a 40% setpoint of the full scale
4: COP or CAV mode with a 50% setpoint of the full scale
5: COP or CAV mode with a 60% setpoint of the full scale
6: COP or CAV mode with a 70% setpoint of the full scale
7: COP or CAV mode with a 80% setpoint of the full scale
16 BITS
0 - 16
8: COP or CAV mode with a 90% setpoint of the full scale
9: COP or CAV mode with a 100% setpoint of the full scale
10: Proportional mode (A configuration)
11: Proportional mode (B configuration)
12: Proportional mode (C configuration)
13: Proportional mode (D configuration)
14: Proportional mode (E configuration)
15: Proportional mode (F configuration)
16: Proportional mode (G configuration)
0: Stop
1: Running
16 BITS
0 – N
2: Alarm (when you try to start de motor (Vreg>1,5V) and it does not
work
16 BITS
18 – 999
Current year if configured before (holding register 40095)
16 BITS
1 – 12
Current month if configured before (holding register 40096)
16 BITS
1 – 31
Current day if configured before (holding register 40097)
16 BITS
0 – 23
Current hour if configured before (holding register 40098)
16 BITS
0 – 59
Current minute if configured before (holding register 40099)
16 BITS
0 – 59
Current second if configured before (holding register 40100)
16 BITS
0 – 65535
Motor alarm counter
16 BITS
0 – 65535
AN1 IAQ alarm counter
16 BITS
0 – 65535
AN2 IAQ alarm counter
16 BITS
0 – 65535
AN3 IAQ alarm counter
16 BITS
0 – 1440
Minutes of device powered
16 BITS
0 – 65535
Days of device powered
16 BITS
0 – 1440
Minutes of device running
16 BITS
0 – 65535
Days of device running
Last motor alarm:
16 BITS
0 – 1
0: No alarm
1: Motor alarm
16 BITS
18 – 999
Year of last motor alarm
16 BITS
1 – 12
Month of last motor alarm
16 BITS
1 – 31
Day of last motor alarm
16 BITS
0 – 23
Hour of last motor alarm
16 BITS
0 – 59
Minute of last motor alarm
16 BITS
0 – 59
Second of last motor alarm
Second to last motor alarm:
16 BITS
0 – 1
0: No alarm
1: Motor alarm
16 BITS
18 – 999
Year of second to last motor alarm
16 BITS
1 – 12
Month of second to last motor alarm
16 BITS
1 – 31
Day of second to last motor alarm
16 BITS
0 – 23
Hour of second to last motor alarm
16 BITS
0 – 59
Minute of second to last motor alarm
16 BITS
0 – 59
Second of second to last motor alarm
Last IAQ alarm:
0: No alarm
16 BITS
0 – 1
1: AN1 IAQ alarm
2: AN2 IAQ alarm
3: AN3 IAQ alarm