• Class 2 power source that complies with the National Electrical Code (NEC),
NFPA 70, clause 725.121 and the Canadian Electric Code (CEC), Part I, c22.1.
Example: Class 2 transformer or class 2 power source in accordance with UL
5085-3/ CSA-C22.2 no. 66.3 or UL 1310/CSA-c22.2 no. 223)
Ambient conditions
• Protect the product from direct sunlight and UV radiation.
6.1.2 Required accessories, materials and tools
Select material and tools that are suitable for your product configuration. De-
pending on the configuration, you will need further accessories.
Mounting material
For mounting, you can use your own mounting material or AVENTICS mounting
material. Respect dimensions and tightening torques.
Tools
• 1x Torx 10 screwdriver
6.2 Preparation
6.2.1 Unpacking and checking the product
1. Check the material number to see if the product matches your order.
2. Check the product for transport and storage damage.
Do not install a damaged product. Return damaged products together with
the delivery documents. See
3. Prepare required accessories, materials and tools.
6.2.2 Implementing safety measures
Procedure
1. Do not carry out any work on the system during preparation.
2. Close off dangerous areas.
3. Make sure the system or system part is not under pressure or voltage.
4. Protect the system against being restarted.
5. Allow product and adjacent system parts to cool down.
6. Wear PPE.
6.3 Installation
The product is preassembled. See
6.4 Connecting the electrical system
Notes
• Observe the pin assignment. See
• Use shielded cables to protect against interference and electrostatic effects.
• Ensure that X7E1 and X7E2 are not connected to the same switch or hub.
• Ensure that no ring topology is manufactured without a ring master.
Procedure
1
Fig. 3: Position of grounding screw
1 Grounding screw
AVENTICS™ Modbus/TCP | 570092-BAL-AB | English
g 4.3 Returning the
product.
g 10. Disassembly and
exchange.
g 11.4 Pin
assignment.
1. Release the grounding screw.
2. Mount the grounding cable using the grounding screw. Screw in grounding
screw.
3. Connect the bus cable to the plug connector X7E1 or X7E2.
Tightening torque: 1.5 Nm + 0.5 Nm
4. Connect the voltage to the plug connector X1S.
Tightening torque: 1.5 Nm + 0.5 Nm
5. Close off all unused ports.
7 Commissioning
7.1 Preparation
General requirements
1. Implement safety measures. See
2. Make sure that all connections are in perfect condition.
3. Check LED. See g 11.3 Display.
7.1.1 Configuring the network
Preparation
Give the product a distinct name in the PLC configuration program.
u
7.1.2 Assigning IP address and subnet mask
Via DHCP server
1. Adjust value 0 on SW1 and SW2.
2. Set address via DHCP.
Via DIP switch
Table 1: Standard settings for IP address
Setting
IP address
Subnet mask
Gateway IP address
1. Release product. See Conversion and extension.
2. Adjust the address on switches SW1 and SW2.
3. Mounting the product See Conversion and extension.
Table 2: Compilation of the IP address for manual setting
Octet
Range
1
192
2
168
3
0 ... 1
4
0 ... 255
SW1 position 2 is not connected.
Table 3: Setting the 4th octet via SW2
Value of the 4th
SW2 positions
octet
1
2
DHCP/BOOTP
0
0
mode
1
1
0
2
0
1
3
1
1
...
...
...
254
0
1
IP address assign-
1
1
ment via website
7.1.3 Configuring the product manually
1. Ensure that the product is not connected to the control.
2. Set at SW2 255. See
g 7.1.2 Assigning IP address and subnet
3. Call up the IP address of the product in a browser.
g 6.2.2 Implementing safety
Value
192.168.0.120
255.255.255.0
192.168.0.1
Setting option
Default value
Default value
SW1, position 1
Default value: 0
SW2, position 1 ... 8, binary
Default value: 0
3
4
5
6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
...
...
...
...
1
1
1
1
1
1
1
1
mask.
measures.
7
8
0
0
0
0
0
0
0
0
...
...
1
1
1
1
18