INSTALLATION MANUAL
CAA480A
Elevator Controller
Figure 14: CAA480A Operation During a Communication Failure:
CAA480A
Elevator Controller
RLY COMMS and RLY OFF/ON
DIP switches are OFF
ADRESS 1
ADRESS 2
ADRESS 4
ADRESS 8
RLY COMMS
RLY OFF/ON
DRM ENABLED
PWR OFF/ON
During a communication failure,
the CAA480A will do nothing.
In order for the RLY OFF/ON DIP switch to be used the RLY COMMS DIP switch must be in the "ON"
position.
13] ENABLING THE DRM MODULE INPUT (DEFAULT: "OFF")
The DRM ENABLED DIP switch (DIP switch 7) will enable the DRM (Destination Reporting
Module) header plug. Once enabled, a DRM can be connected directly
to the CAA480A's DRM header plug. Refer to Figure 15 for more details.
For more information on the DRM please refer to Destination Reporting Module (DRM)
on page 21.
Figure 15: DRM DIP Switch:
The RLY COMMS DIP switch (DIP switch 5) enables relay
ADRESS 1
ADRESS 2
control during a communication failure.
ADRESS 4
ADRESS 8
RLY COMMS
RLY OFF/ON
The RLY OFF/ON DIP switch (DIP switch 6) determines
DRM ENABLED
PWR OFF/ON
whether the floor control relays are activated or
RL 10
RL 11
deactivated during a communication failure.
The RLY COMMS DIP switch is ON
The RLY OFF/ON DIP switch is OFF
ADRESS 1
ADRESS 2
ADRESS 4
ADRESS 8
RLY COMMS
RLY OFF/ON
DRM ENABLED
PWR OFF/ON
During a communication failure,
the CAA480A will deactivate
all floor relays
that are currently activated
ADRESS 1
ADRESS 2
ADRESS 4
ADRESS 8
RLY COMMS
RLY OFF/ON
DRM ENABLED
PWR OFF/ON
RLY COMMS and RLY OFF/ON
During a communication failure,
the CAA480A will activate all floor
relays that are currently deactivated
Enable the DRM header plug by
placing the DRM ENABLED DIP
switch (DIP switch 7) in the ON
position.
DIP switches are ON
ADRESS 1
ADRESS 2
ADRESS 4
ADRESS 8
RLY COMMS
RLY OFF/ON
DRM ENABLED
PWR OFF/ON
cdvigroup.com
EN
17