INSTALLATION MANUAL
CAA480A
Elevator Controller
10] 350MA/700MA BATTERY CHARGING JUMPER (DEFAULT "350MA")
This jumper allows you to select the charging current for the backup battery
of the CAA480A. Charging the battery at 350mA will take longer, but consumes
less power from the CAA480A. Charging the battery at 700mA takes less time,
but consumes more power from the CAA480A. Refer to Figure 10.
Figure 10: 350mA/700mA Battery Charging Jumper:
+
350mA/700mA
11] EMERGENCY CONTROL (FC) OVERRIDE JUMPER (DEFAULT "ON")
This jumper determines the CAA480A's emergency control override input. When this
jumper is "ON", even if there is an emergency circuit connected to the CAA480A's
emergency control input ("FC" terminals), the CAA480A will ignore any signals coming to
the "FC" terminals. Refer to Figure 11 for more details.
!
!
If you are not using the CAA480A's Emergency Control terminals then the FC Override jumper should
be in the "ON" position. This will allow for full power to be supplied to the floor control relays.
Figure 11: Emergency Control (FC) Override Jumper:
FC OVERRIDE
C
ERSED
LAY
T
!
!
If you are employing Emergency Control with the CAA480A, be sure to wire the floor control relays
using the Fail-Safe method. Refer to "Fail-Safe" on page 8 for more information.
+
+
+
+12V
GND
GND
FC
FC
Emergency Control (FC) Override Jumper
ENABLED
FC OVERRIDE
Battery Charging Jumper Settings
350mA
350mA/700mA
DISABLED
FC OVERRIDE
EN
700mA
350mA/700mA
13