2.4 Gas connection
The gas must be connected to the relevant connection (see cap. 4.1 "Dimensions and connections") in conformity with
current regulations, with a rigid metal pipe or with a continuous flexible s/steel tube, installing a gas cock between the
system and boiler. Make sure all the gas connections are tight.
2.5 Electrical connections
ATTENTION
BEFORE CARRYING OUT ANY OPERATION REQUIRING REMOVAL OF THE
B
CASING, DISCONNECT THE BOILER FROM THE ELECTRIC MAINS WITH
THE MAIN SWITCH.
NEVER TOUCH THE ELECTRICAL COMPONENTS OR CONTACTS WITH THE
MAIN SWITCH TURNED ON! DANGER OF ELECTRIC SHOCK WITH RISK OF
INJURY OR DEATH!
The unit must be connected to an efficient grounding system in accordance with
B
applicable safety regulations. Have the efficiency and suitability of the grounding
system checked by professionally qualified personnel; the Manufacturer declines
any liability for damage caused by failure to ground the system.
The boiler is pre-wired and equipped with a three-core connection cable to the
electric line without plug. The connections to the grid must be made with a perma-
nent connection and equipped with a bipolar switch with contact opening of at least
3 mm, interposing fuses of max. 3A between the boiler and line. Make sure to res-
pect the polarities (LINE: brown wire / NEUTRAL: blue wire / GROUND: yellow-
green wire) in the connections to the electric line.
The unit's power cable MUST NOT BE REPLACED BY THE USER. If the cable
B
gets damaged, turn the unit off and have the cable replaced only by profes-
sionally qualified personnel. In case of replacement, use exclusively "HAR H05
VV-F" 3x0.75 mm2 cable with maximum ext. diameter of 8 mm.
Room thermostat (optional)
IMPORTANT: THE ROOM THERMOSTAT MUST HAVE VOLTAGE-FREE CON-
B
TACTS. CONNECTING 230 V TO THE ROOM THERMOSTAT TERMINALS
WILL PERMANENTLY DAMAGE THE ELECTRONIC BOARD.
When connecting time controls or a timer, do not take the power supply for these
devices from their breaking contacts Their power supply must be by means of di-
rect connection from the mains or with batteries, depending on the kind of device.
38
cod. 3542B920 - Rev 07 - 06/2024
DIVA D C24
EN