4.0 Installation
4.1 General
After unpacking, check the PinTherm Mistral and the sensors (if applicable) for damage. Check that the
type/model and the rated voltage are correct.
4.2 Installation PinTherm Mistral
Determine a suitable place for installing the PinTherm Mistral. Mount the PinTherm Mistral on a solid
surface that can carry a minimum of 4 kg. We recommend mounting the PinTherm Mistral at a height of
±1.5m from the floor, at a well reachable place.
For cable gland use only cable glands fitted with strain relief, with a minimum fire class of UL94V2.
Check that the power supply has been switched off before connecting any wiring. If this is not the case,
the power supply must be switched off before you continue. When switching off the power supply of
the appliance to which connection is to be made, you should also refer to the technical documentation/
operating instructions for the appliance in question.
Connect the PinTherm Mistral according to one of the supplied electrical diagrams which are in the back
of this technical book. To select the correct connection diagram, you need to know on which type of
device you will connect the PinTherm Mistral. For a selection see also Annex I.
When applying a 0-10VDC signal, see the table below for the correct cable diameter and associated
length.
Diameter
Length
0.8mm
2
80 meter
1.0mm
2
100 meter
1.5mm
2
150 meter
4.3 Installation external room sensor (06 29 086)
Place the external room sensor draft-free, in view of the appliance at a height of approx. 1.5m from the
floor. And connect the sensor to the appropriate terminals in the PinTherm Mistral. Refer to the chart
below for the correct wire diameter and length.
Diameter
Length
2
0.8mm
80 meter
2
1.0mm
100 meter
1.5mm
2
150 meter
6
0-10V max (5-10V): 10.0 V
: Setpoint cooling 15°C
Setpoint heating 30°C
: Room temperature +0.0 K
Water temperature -0.0 K
: DX
: 1000
: Slave ID 001
: Static 192.168.1.100
Start bit :
1
Stop bit :
1
Parity :
None
Baud rate :
9600
In this case, we advise the use of a shielded cable.
In this case, we advise the use of a shielded cable.