5.8 Enter or change switching times
SET/CHANGE
PROGRAM
MONDAY
--:-- -> --:--
changes the
flashing digit
to go up one digit
5.9 Switch delay
SWITCH DELAY
select
Setting of the the delay between heating and cooling mode and vice versa.
Possible settings: 0 minutes, 15 minutes or 30 minutes.
5.10 Control settings cooling
CONTROL SETTINGS
COOLING
0-10V MIN(0-5V)
changes the
flashing digit
to go up one digit
*
This function determines when the 0-10VDC signal is modulated back in conditions of heat
demand. When set to 1.0, the PinTherm Mistral will start to modulate the 0-10V signal at 1K below
the target temperature. The range can be set between 0.5 - 3.0 and is set to 1.0 as standard.
**
When there is no heating/cooling demand, the PinTherm Mistral sends out a signal of 0VDC.
MONDAY
07:30 -> 17:00
OK
changes the
flashing digit
to go up one digit
3
TUESDAY
07:30 -> 17:00
OK
OK
OK
**
0.0 V
OK
1
MONDAY
--:-- -> --:--
OK
1
SUNDAY
etc.
--:-- -> --:--
SWITCH DELAY
30 MIN
changes the
flashing digit
to go one digit up
0-10V RANGE(1-3)
1.0 K
changes the
flashing digit
to go up one digit
0-10V MAX(5-10V)
7.0 V
changes the
flashing digit
to go up one digit
2
OK
3
OK
back to the
menu
OK
back to the
menu
*
OK
OK
back to the
menu