8 Troubleshooting
Error code
Description
F0
Fault with the fan motor on the outdoor unit (DC motor)
F1
Fault with the inverter module protection (IPM)
F2
Fault with the outdoor unit board protection (PFC) condenser
F3
Fault with the compressor synchronism
F4
Fault with the discharge temperature sensor
F5
Fault with the overheating protection on the compressor
F6
Fault with the outdoor temperature sensor
F7
Fault with the over-voltage or low voltage protection
F8
Communication fault between the outdoor unit and the outdoor unit control board unit
F9
Fault with the outdoor unit EPROM
FA
Suction sensor error
Fb
Floor standing motor error.
P2
High-pressure switch protection
P3
Lack of refrigerant protection
P4
Condenser overload protection (cooling mode)
P5
Discharge temperature protection
P6
Evaporator overload protection (heating mode)
P7
Indoor unit freeze protection (cooling mode)
P8
Outdoor unit overcurrent protection
1
2
Tab.92
Outdoor unit error codes
LED 1
LED 2
130
Additional information regarding the errors is given via the LEDs on the
outdoor unit PCB :
1. Check the LED signals and refer to following table for error
2. Remove the panel of the PCB support.
3. Check signals on the LED.
LED representation:
MW-6020074-01
LED 3
Error name
Normal (outdoor unit standby)
Normal (compressor running)
Forced service (test mode)
Module protection error
Compressor out-of-step error
Exhaust air sensor error
description.
OFF
ON
Flashing
Probable Trouble Location
Normal, all three lights off for standby status.
Normal, all three lights flash while compressor
running.
Normal
Power voltage, compressor cable, reactor, mod
ule panel, main external control panel, compres
sor.
Power voltage, compressor cable, module panel,
main external control panel, compressor.
System pressure, exhaust air sensor, main exter
nal control panel.
7797831 - v04 - 07122022