Unitary capacity
Rated Battery Voltage
Backup time with 50%
linear load
Battery extension
Maximum charge current
Recharge time (to 90%)
Communication and management
Screen and signalling
Communications ports
Software
Protections
Mechanical characteristics
Dimensions W x H x D (mm) 440 x 88 (2U) x 405
Net weight (kg)
Environmental conditions
Operating temperature
Operating relative humidity
Storage temperature
Noise level at 1 m
IP code
Heat dissipation (BTU/h)
Reference directive and standards
Safety
EMC
Performance and test
requirements
3 101 70
12 Vdc - 7.2 Ah
36 Vdc
> 10 min
2.1 Adc
six pushbuttons and four LEDs for real-time control of the status
and the main parameters of the UPS
Connector for network interface
Software for Windows and Linux environments is available in order to:
- displaying all the functioning and diagnostic data in case of problems;
- setup of special functions.
Download a copy free of charge from the website
http://www.ups.legrand.com
Electronic circuits against overloads and short-circuit
Emergency Power Off (EPO)
16
20% to 80% (non-condensing)
490
DAKER DK Plus
1 kVA - 2 kVA - 3 kVA
3 101 71
12 Vdc - 7.2 Ah
72 Vdc
> 10 min
Yes
1.5 Adc
4 hours
RS232 and USB
Backfeed
Overtemperature
440 x 88 (2U) x 600
29,5
0 ºC to +40 ºC
+32 ºF to +104 ºF
0 ºC to +50 ºC
+32 ºF to +122 ºF
< 50 dB
IP 21
654
2014/35/EU Directive
EN 62040-1
2014/30/EU Directive
EN 62040-2
EN 62040-3
3 101 72
12 Vdc - 9 Ah
72 Vdc
> 8 min
1.5 Adc
30
818
61