1.0 Introduction
1.1 Kit Contents
The Kozy Heat Interior Heat Transfer Kit (#HTK-INT) is de-
signed to mount inside of the house and transfer heat to
different room(s), or locations within a room.
The following model(s) allow a maximum installation of two
interior heat transfer kits: #ABY, #ALP-36S, #BHM-38, #BHM
-38-BW, #BHM-44, #BHM-44-BW, #BHM-52, #BHM-52-BW,
#CAR-39, #CAR-46, #CLW-40, #CLW-50, #CLW-50-MV, #CLW
-72, #CLW-ST, #NDK-60TL, #SFD-36, #Z42, and #Z42-CD.
Fan assembly must be installed on interior walls or ceiling
only. Installation in the floor is not recommended. Fan
wheel must be installed in the horizontal plane. Do not in-
stall with fan axis mounted vertically.
Amount of heat delivered depends on many factors such as:
Length, type, and location of pipe (avoid running pipe
through unheated areas - insulate pipe if doing so).
Number of elbows.
Duration of fireplace operation.
Elevation of fan relative to heater (note: using the re-
mote fan will affect the heat output at the fireplace).
1.2 Installation
1.2.1 Installation Precautions
This device must be installed by a qualified installer in ac-
cordance with these instructions and in accordance with
local codes, if any, and with National Electrical Code ANSI/
NFPA 70, current edition.
The #HTK-INT fan will generate sound during operation. The
effects of the increased sound level can be minimized with
careful planning during installation of the system.
CAUTION: Wear protective gloves and safety gloves during
installation. Sheet metal edges are sharp.
Disconnect electrical power supply before performing any
maintenance, repair, or electrical wiring.
WARNING: Failure to install, operate, and maintain the inte-
rior heat transfer system in accordance with manufacturer's
instructions will result in conditions which may produce
bodily injury and/or property damage.
HTK-INT
1.2.2 Installation Guidelines
NOTE: Support duct at intervals of no greater than 4 feet,
with no more than 1/2" sag between supports as required
by local code.
Do not substitute any other duct work as a replacement for
the provided insulated flexible duct.
Minimum Duct Run Length:
3 ft (914mm)
Models: #ALP-36S, #BHM-38, #BHM-38-BW, #BHM-44,
#BHM-44-BW, #BHM-52, #BHM-52-BW, #CAR-39, #CAR-46,
#CLW-40, #CLW-50, #CLW-50-MV, #CLW-72, #CLW-ST,
#NDK-60TL, & #SFD-36
8 ft (2.4m)
Models: #ABY, #Z42, & #Z42-CD
Maximum Duct Run Length:
25 ft (7.8m)
Models: All approved models
Clearance to flexible duct:
0 in (0mm)
IMPORTANT: The insulated flexible pipe is zero clearance
to combustible but CANNOT be compressed into a smaller
diameter.
1.2.3 Painting Requirements
The #HTK-INT air grille may be painted to a desired color, as
long as the paint selected has sufficient temperature and
environmental ratings.
Thoroughly sand the existing coating prior to painting
with sandpaper or steel wool.
The front of the air grille may be field-painted and
cured up to 250 degrees Fahrenheit (121°C).
3
Rev. 14 — April 2024