ELMON relay 31-31
Safety Relay
6.3 Test
For a standard-compliant design of the protecti on, the primary machine control must perform a test prior
to each dangerous movement or during the non-dangerous phase/movement of the machine. Upon appli-
cati on of the test signal, the output terminal of the switching unit must open. This change in switching state
must be evaluated by the primary machine control . If the test result is correct, the machine control then
initi ates the movement or the next work step. Otherwise, the control must output an error message and
the power-driven work equipment (e.g. motor) must receive a switch-off signal from the machine control.
The available test signal can be selected with the DIP slide switch.
DIP slide switch S1
6.4 Wiring opti ons
U
12 V . . . 28 V AC/DC
Test
With testi ng by the control, the
ments in accordance with EN ISO 13849-1:2015 "Safety-related parts of control
systems" .
Without testi ng, the operati on or wiring of the ELMON relay 31 sati sfi es no specifi c
safety requirement.
Test signal connecti on terminals
AC/DC
AC/DC
ELMON relay
Characteristi cs of the signal
Test signal S1 Pos . "A"
Test signal S1 Pos . "B"
Switching outputs
DC
DC
31 system sati sfi es the Cat. 2 require-
17