Function settings (continued)
No.36
Outdoor temperature display setting
Set to display outdoor temperature detected by Lossnay unit
thermistor or not.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
36
-
-
No.37
Indoor temperature display setting
Set to display indoor temperature detected by Lossnay unit thermistor
or not.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
37
-
-
Calculated supply air temperature display
No.38
setting
Set to display calculated supply air temperature or not.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
38
-
-
Temperature exchange efficiency
No.39, 40
setting
Set the 10 digit of temperature exchange efficiency which is used to
calculate supply air temperature.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
39
-
-
-
-
-
-
-
-
-
-
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
40
-
-
-
-
-
-
-
-
-
-
Setting
Outdoor temperature
check
display
0
N/A
(Factory setting)
Display on the screen of
1
PZ-61DR-E
Setting
Indoor temperature
check
display
0
N/A
(Factory setting)
Display on the screen of
1
PZ-61DR-E
Setting
Calculated supply
check
temperature display
0
N/A
(Factory setting)
Display on the screen of
1
PZ-61DR-E
Setting
10 digit of temperature
check
exchange efficiency
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
(Factory setting)
8
8
9
9
Setting
1 digit of temperature
check
exchange efficiency
0
0
(Factory setting)
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
No.41
Outdoor temperature correction
Set the correction for the outdoor temperature displayed on the
PZ-61DR-E screen by function
No. 36
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
41
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No.42
Indoor temperature correction
Set the correction for the indoor temperature displayed on the
PZ-61DR-E screen by function
No. 37
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
42
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No.51
Automatic ventilation mode setting
Set the pattern of conditions to go into By-pass mode in automatic
ventilation operation.
When setting Data is set "3" by PZ-61DR-E, function
and
No. 54
are available.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
(Factory setting)
SW2-7
51
ON
-
-
* Pattern A is more likely to become By-pass mode than pattern B.
.
Setting
The correction to
check
thermistor detection
0
19 ˚F (-7 ˚C)
1
21 ˚F (-6 ˚C)
2
23 ˚F (-5 ˚C)
3
25 ˚F (-4 ˚C)
4
27 ˚F (-3 ˚C)
5
28 ˚F (-2 ˚C)
6
30 ˚F (-1 ˚C)
7
32 ˚F (0 ˚C)
(Factory setting)
8
34 ˚F (+1 ˚C)
9
36 ˚F (+2 ˚C)
10
38 ˚F (+3 ˚C)
11
40 ˚F (+4 ˚C)
12
41 ˚F (+5 ˚C)
13
43 ˚F (+6 ˚C)
14
45 ˚F (+7 ˚C)
.
Setting
The correction to
check
thermistor detection
0
19 ˚F (-7 ˚C)
1
21 ˚F (-6 ˚C)
2
23 ˚F (-5 ˚C)
3
25 ˚F (-4 ˚C)
4
27 ˚F (-3 ˚C)
5
28 ˚F (-2 ˚C)
6
30 ˚F (-1 ˚C)
7
32 ˚F (0 ˚C)
(Factory setting)
8
34 ˚F (+1 ˚C)
9
36 ˚F (+2 ˚C)
10
38 ˚F (+3 ˚C)
11
40 ˚F (+4 ˚C)
12
41 ˚F (+5 ˚C)
13
43 ˚F (+6 ˚C)
14
45 ˚F (+7 ˚C)
No. 52
,
No. 53
Setting
Conditions to go into
check
By-pass mode
0
DIP-SW priority
(Factory setting)
Pattern A
Indoor temperature is 61 ˚F (16 ˚C) or more
1
Outdoor temperature is 61 ˚F (16 ˚C) or more
Indoor temperature - outdoor
temperature ≥ 32 ˚F (0 ˚C)
Pattern B
Indoor temperature is 72 ˚F (22 ˚C) or more
2
Outdoor temperature is 64 ˚F (18 ˚C) or more
Indoor temperature - outdoor
temperature ≥ 36 ˚F (2 ˚C)
3
Free setting
Eng-17
,