Installation method (continued)
4
By-pass monitor or Pre-heater signal output.
By-pass monitor or Pre-heater signal can be selected at SW5-6.
(Refer to function settings
No. 58
Always check that it is the intended setting.
By-pass monitor SW5-6 OFF
By-pass operation
indicator
Max 240 VAC, 1 A
24 VDC, 1 A
Min
208 VAC, 100 mA
Power
5 VDC, 100 mA
Supply
Pre-heater output SW5-6 ON
2.2 yd (2 m) or more
Lossnay
OA
Pre-heater
Relay
Power Supply
Power Supply
for heater
for relay
CAUTION
• Select a duct heater in compliance with local and national
laws, ordinances, and standards.
Select a duct heater that meets adequate standard in each
country.
• Always select a heater that is equipped with a non-self-
resetting safety device.
Do not directly supply power from the Lossnay unit to the
duct heater.
(Doing so could cause fire.)
• Install a circuit breaker for the duct heater in compliance with
all applicable laws, ordinances, and standards.
• Install the duct heater separated from the product by a
distance of 2.2 yd (2 m) or more.
(Failure to do so may result in equipment damage due to the
transmission of residual heat from the heater.)
• When using a heater without a temperature control function,
select a heater with a capacity that is matched to the air
volume.
• Do not use the heater outside the set air volume.
(If the heater's capacity is too larger, this may result in the
heater frequently turning ON/OFF.)
(If the heater's capacity is too small, this may result an
inability to heat.)
• Ensure that the duct heater and Lossnay are wired and that
the Lossnay function settings have been configured, and then
always check operation by trial operation.
• For the duct heater output, see function setting SW5-6.
5
Malfunction monitor output.
TM3
Malfunction indicator
Power
Max 240 VAC, 1 A
Supply
24 VDC, 1 A
Min
208 VAC, 100 mA
5 VDC, 100 mA
)
TM3
7
8
9
X13
10
SA
TM3
7
8
9
X13
10
Max 240 VAC, 1 A
24 VDC, 1 A
Min
208 VAC, 100 mA
5 VDC, 100 mA
7
8
9
X14
10
6
Operation monitor output
Operation monitor output can be selected to sympathize with exhaust
fan or supply fan at SW 5-2.
SW5-2 OFF: Exhaust fan operation monitor output
SW5-2 ON: Supply fan operation monitor output
(Refer to function settings
No. 57
Always check that it is the intended setting.
TM3
Operation
indicator
Power Supply
Max 240 VAC, 1 A
24 VDC, 1 A
Min
208 VAC, 100 mA
5 VDC, 100 mA
To use operation monitor output for a supply after-heater, turn SW2-8
ON, and use the supply fan operation monitor output with delayed
operation. (Refer to function settings
For the heater, observe the cautions listed in 4 .
Lossnay
OA
Power Supply
for heater
When switching fan speed externally
7
(when a sensor or other equipment is connected)
Using a field supply sensor, etc., make connection by inserting the
optional remote display adaptor (PAC-SA88HA-E or PAC-725AD) in
the connector CN17 (Red) as shown by the figure.
Lossnay will operate the fan speed following the table below,
regardless of the remote controller setting.
CN17 (Red)
Fan speed
1-2 (Brown-Red)
4
1-3 (Brown-Orange)
3
1-4 (Brown-Yellow)
2
1-5 (Brown-Green)
1
n Example "Fan speed 4"
Remote display adaptor
(Optional) PAC-SA88HA-E
Field supply sensor, etc.
or PAC-725AD
SW1
Orange 3
Not used. Insulate completely.
Max wiring length 11 yd (10 m)
Use this in such a way that it ventilates at low fan speed normally,
and when the external sensor detects contamination of indoor air,
it changes to high fan speed operation.
)
7
8
9
X15
10
No. 57
)
2.2 yd (2 m) or more
SA
TM3
7
8
Relay
9
X15
10
Power Supply
Max 240 VAC, 1 A
for relay
24 VDC, 1 A
Min
208 VAC, 100 mA
5 VDC, 100 mA
Lossnay
control board
Brown 1
CN17
Red 2
Yellow 4
Fan speed
Green 5
selection
Eng-11