CONSTRUCTION SPECIFICATIONS
Electrical specifications on output with battery operation
Rated output voltage
Output frequency
Active output capacity on non-linear load
Apparent output capacity on non-linear load
Battery operation
Operating time to 80% of the load
Charging time
Technical data and number of batteries
Standards
Electromagnetic compatibility
Emission - Immunity
Safety
Performance and features
NOTICE
The batteries are considered hazardous waste and should be disposed of in accordance with
current regulations.
20
®
9 Technical features
3 100 04
3 100 13
3 100 26
230 V ± 10 %
50/60 Hz ± 1Hz
600 W
1100 VA
5 min.
10/12 h at the end of operating range
n° 2
maintenancefree,
sealed, leadacid
batteries 12V
7,2 Ah
Conforms to EN 62040 - 2
Conforms to EN 62040 -1 -1
Conforms to EN 62040 -3
3 100 05
3 100 14
3 100 27
900 W
1500 VA
5 min.
n°2
maintenance-free,
sealed, lead-acid
battery 12V
9 Ah