9 Technical features
CONSTRUCTION SPECIFICATIONS
Weights
Dimensions L x H x P in mm
Protection
Ambient specifications
Operating temperature range
Operating relative humidity range
Degree of protection as per IEC529
Noise level at 1 meter
Electrical input specifications
Rated input voltage
Range of input voltage
Rated input frequency
Maximum input current
Number of input phases
Waveform on output
With battery operation
Type of operation
Electrical specifications on output
Rated output voltage
Output current on nominal load
Apparent output capacity on nominal load
Apparent output capacity on nominal load
Overload capacity
Number of phases on output
Niky 1000/1500
3 100 04
3 100 13
3 100 26
13 Kg.
147 x 239 x 354
Electronic protection against overloading
and short-circuiting. Shutdown on
reaching operating limit and overheating.
Automatic shutdown due to protection
triggering
from 0 to +40 °C
from 0 to 95% non-condensing
IP20
< 40 dBA
230 V
175-285VAC
50-60 Hz +/-5Hz
6,2 Arms
Single phase
step wave
line interactive
230 V ± 10 %
4,7 Arms
600 W
1000 VA
110% for 5 s.
Single phase
3 100 05
3 100 14
3 100 27
16 Kg.
8,5 Arms
6,5 Arms
900 W
1500 VA
19