Connection terminal allocation
• Loosen the screws and remove the converter
cover.
Designation
Allocation
L1, L2, L3
Mains connection voltage
PE
Earth connection
IN1
Sensor input
IN2
External setpoint input
GND (x2)
Ground connections
+ 24 V
DC voltage for sensor
Ext. off
Control input (ON/OFF)
« Overriding Off »
for external potential-free switch
SBM
« Available transfer » relay
SSM
« Failures transfer » relay
PLR
Connection terminals of the interface
PLR
LON
Connection terminals of the interface
LON
NOTE: The terminals IN1, IN2, GND and Ext. Off
meet the requirement for "isolated secondary
circuits, limited voltage/limited current" (accord-
ing to UL508C and EN 61800-5-1) to the mains
terminals, as well as to the SBM and SSM termi-
nals (and vice versa).
WILO SE 05/2014
Notes
Three-phase current 380,400,480 V per IEC 38
Type of signal: Voltage (0 - 10 V, 2 - 10 V)
Input resistance: Ri ≥ 10 kΩ
Type of signal: currrent (0 - 20 mA, 4 - 20 mA)
Input resistance: R
= 500 Ω
B
Can be configured in the « Service » menu <5.3.0.0>
Type of signal: Voltage (0 - 10 V, 2 - 10 V)
Input resistance: Ri ≥ 10 kΩ
Type of signal: currrent (0 - 20 mA, 4 - 20 mA)
Input resistance: R
= 500 Ω
B
Can be configured in the « Service » menu <5.4.0.0>
For both inputs IN1 and IN2
Load max. : 60 mA
The voltage is short-circuit proof
The pump can be switched on/off via the external
potential-free contact.
In systems with a high switching frequency
(> 20 switch-ons/offs/day), switching on/off is to be
done via « ext. off ».
In normal operating, the relay is activated when the
pump runs or is in a position to run.
When a first defect appears or by main supply cutoff (the pump
stops), the relay is deactiveated.
Information is given to the control box, regarding the availability of
the pump, even temporarily.
Can be configured in the « Service » menu <5.7.6.0>
Contact load:
minimum: 12 V DC, 10 mA
maximum: 250 V AC, 24DC, 1 A
After a series of detection (from 1 to 6 according to
significance) of the same type of defect, the pump
stops and this relay is activated and requires manual override.
Contact load:
minimum: 12 V DC, 10 mA
maximum: 250 V AC, 24DC, 1 A
The optional IF-Module PLR is to be pushed into the
multiplug in the connection area of the converter.
The connection is twist-proof.
The optional IF-Module LON is to be pushed into the
multiplug in the connection area of the converter.
The connection is twist-proof.