Sagi ME70LTR Manuel D'utilisation Et D'installation page 248

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 43
CA1
-25
25
CA2
-25
25
P0
0
1
P1
0
1
P2
0
1
P4
0
3
P5
0
4
P8
0
250
LABEL
MIN.
MAS.
r0
0.1
15
r1
-99
r2
r2
r1
199
r4
0
99
r5
0
1
r12
0
1
LABEL
MIN.
MAS.
C0
0
240
C2
0
240
C3
0
240
C4
0
240
C5
0
240
C6
0
199
C7
0
199
C8
0
15
C10
0
999
LABEL
MIN.
MAS.
d0
0
99
d1
0
2
d2
-99
99
d3
0
99
d4
0
1
d5
0
99
d6
0
2
d7
0
15
d8
0
3
d9
-99
99
d11
0
1
°C/°F (1)
room probe offset
°C/°F (1)
if P4 = 1 or 2, evaporator probe offset;if P4 = 3, condenser probe offset
-
probe type (0 = PTC; 1 = NTC)
degree Celsius decimal point (during normal operation)
-
1 = YES
unit of measurement for temperature (2)
-
0 = °C (Celsius degree; resolution depends on P1 parameter)
1 = °F (Fahrenheit degree; resolution is 1 °F)
second analog input function
0 = absent
-
1 = evaporator probe (defrost probe and probe determining the activity of the evaporator fan)
2 = evaporator probe (probe determining the activity of the evapor. fan)
3 = condenser probe
magnitude displayed during normal operation
0 = room temperature
1 = working setpoint
-
2 = if P4 = 0, "- - -"
if P4 = 1 or 2, evaporator temperature
if P4 = 3, condenser temperature
0,1 s
delayed display of temperature changes as detected by the probes
U.M.
MAIN REGULATOR
°C/°F (1)
working setpoint differential; see also r12
°C/°F (1)
minimum working setpoint
°C/°F (1)
maximum working setpoint
working setpoint increase during the "energy saving" function; see also i0, i10 and HE2
°C/°F (1)
-
cooling or heating operation (3)
0 = cooling
1 = heating
-
working setpoint differential type
0 = asymmetric
1 = symmetric
U.M.
COMPRESSOR PROTECTION SYSTEM
min
delay in switching on of compressor after the device switches on (4)
min
minimum compressor switch-off duration (5)
s
minimum duration of compressor switch on time
duration of compressor switch off time during a room temperature probe error (code "Pr1"); see also C5
min
duration of compressor switch on time during a room temperature probe error (code "Pr1"); see also C4
min
°C/°F (1)
condenser temperature is higher than that at which the condenser overheating alarm is activated (code
"COH") (6)
condenser temperature above which the compressor shut down alarm is activated (code "CSd")
°C/°F (1)
compressor shut down alarm delay (code "CSd") (7)
min
10 h
compressor operation hours to signal service for compressor is required
0 = function disables
U.M.
DEFROST
if d8 = 0, 1 or 2, defrost interval
h
0 = interval defrost will never be activated
if d8 = 3, maximum defrost interval
type of defrost
0 = ELECTRIC - during defrost the compressor will remain off and the defrost output will be activated;
evaporator fan activity will depend on F2 parameter
-
1 = BY HOT GAS - during defrost the compressor will be switched on and the defrost output will be
activated; evaporator fan activity will depend on F2 parameter
2 = VIA STOPPING OF COMPRESSOR - during defrost the compressor will remain switched off and
the defrost output will remain deactivated; evaporator fan activity will depend on F2 parameter
°C/°F (1)
evaporator temperature at end of defrost; see also d3
if P4 = 0, 2 or 3, defrost duration
min
if P4 = 1, maximum defrost duration; see also d2
0 = defrost will not be activated
defrost when device is switched on (4)
-
1 = YES
if d4 = 0, minimum time between switching on of device and activation of defrost (4)
min
if d4 = 1, delay in activation of defrost after device is switched on (4)
temperature displayed during defrost (only if P5 = 0)
0 = room temperature
1 = if on activation of defrost, the room temperature is below the "work setpoint + + Δt", at maximum "
-
work setpoint + Δt"; if on activation of defrost, the room temperature is above "work setpoint + Δt", at
maximum the room temperature on activation of defrost (8) (9)
2 = label "dEF"
dripping duration (during dripping the compressor will remain switched off and the defrost output will
min
remain deactivated; evaporator fan activity will depend on F2 parameter)
defrost activation methods
0 = AT INTERVALS - FOR TIME - defrost will be activated once the device has altogether been
running for time d0
1 = AT INTERVALS - FOR COMPRESSOR SWITCH-ON - defrost will be activated once the
compressor has altogether been switched on for time d0
-
2 = AT INTERVALS - FOR EVAPORATOR TEMPERATURE - defrost will be activated when the
evaporator temperature has remained below the temperature d9 for a total time of d0 (10)
3 = ADAPTIVE - defrost will be activated at intervals, whose duration will each time depend on the
duration of compressor switch-ons, the evaporator temperature and the door switch input activation;
see also d18, d19, d20, d22, i13 and i14 (10)
evaporator temperature is higher than that at which the defrost interval counter is suspended (only if d8
°C/°F (1)
= 2)
defrost alarm switches off once maximum time limit has been reached (code "dFd"; only if P4 = 1 and
-
16

Publicité

Table des Matières
loading

Produits Connexes pour Sagi ME70LTR

Table des Matières