I2
-1
120
I3
-1
120
I10
0
999
I13
0
240
I14
0
240
LABEL
MIN.
MAS.
HE2
0
999
HE3
0
240
LABEL
MIN.
MAS.
POF
0
1
PAS
-99
999
(1) the unit of measurement depends on P2
(2) properly set the parameters corresponding to the regulators after setting P2 parameter
(3) if r5 parameter is set at 1, the "energy saving" function and the defrost management will be switched off; see also F1 parameter
(4) the parameter has effect even after an interruption in the power supply that occurs while the device is switched on
(5) the time set by paramenter C2 is counted also when the device is off
(6) the differential of parameter is 2.0°C/4°F
(7) if when the device is switched on, the condenser temperature is already above that established in C7 parameter, then C8 parameter will not have effect
(8) the value Δt depends on r12 parameter (r0 if r12 = 0, r0/2 if r12 = 1)
(9) the display restores normal operation when, at the end of the dripping phase, room temperature falls below the value that locked the display (or if a temperature
alarm is triggered)
(10) if P4 parameter is set at 0, 2 or 3, the device will function as if d8 parameter were set at 0
(11) if when defrost is activated, the operating duration of the compressor is less than the time established with d15 parameter, the compressor will remain on for the
amount of time necessary to complete defrost, then the defrost shall be activated
(12) during defrost, dripping and evaporator fan standstill, the maximum temperature alarm is absent, provided that it was triggered after defrost activation.
(13) during activation of the door switch input, the maximum temperature alarm is absent, provided the alarm was signaled after the activation of the input
(14) F4 and F5 parameters have effect when the compressor is off
(15) F4 and F5 parameters have effect when the compressor is on
(16) if P4 parameter is set at 2, the device will function as if F0 parameter were set at 2
(17) F4 and F5 parameters have effect when the evaporator temperature is below the temperature established with F1 parameter
(18) F4 and F5 parameters have effect when the compressor is on and the temperature of the evaporator is below the temperature established with F1 parameter
(19) the compressor is switched off 10 s after the activation of the input; if the input is activated during defrost or when the evaporator fan is deactivated, the activation
will not have any effect on the compressor.
Setting the working setpoint
•
Make sure that the keyboard is not locked and that no procedure is in progress
•
Touch the
•
Touch the
or
•
Touch the
To exit the procedure before the operation is complete:
• Touch the
(any changes will not be saved)
The working setpoint can also be set via SP parameter.
Working setpoints
LABEL
MIN.
MAS.
r1
r2
Setting the configuration parameters
To access the procedure:
•
Make sure no procedure is in progress
•
Touch the
•
Touch the
•
Touch the
or
default)
•
Touch the
if i0 = 1 or 2, delay in signalling of door switch input alarm (code "id")
-1 = the alarm will not be signalled
if i0 = 4, delay in signalling of multifunction input alarm (code "iA")
min
-1 = the alarm will not be signalled
if i0 = 5, delay in switching on of compressor after the deactivation of the maximum pressure switch
alarm (code "iA")
-1 = reserved
maximum duration of the effect caused by the activation of the door switch input on the compressor
min
-1 = the effect will last until the input is deactivated
time that must pass in absence of door switch input activations (after the room temperature has
reached the working setpoint) for the "energy saving" function to be activated; see also r4, F4, F5 and
min
HE2
0 = the function will never be activated due to the effect of this condition
number of door switch input activations such as to provoke the defrost activation
-
0 = defrost will never be activated due to the effect of this condition
minimum duration of the door switch input activation such as to provoke the defrost activation
min
0 = defrost will never be activated due to the effect of this condition
U.M.
ENERGY SAVING
maximum duration of the "energy saving" function activated due to the effect of absence of door switch
min
input activation; see also r4, F4, F5 and i10
0 = the function will last until the input is activated
time interval with no key strokes, after which the "low consumption" function is activated
min
0 = the mode shall never be aactivated
U.M.
VARIOUS
-
key activation
access password for the configuration parameters
min
0 = the password need not be set
NEGATIVE TEMPERATURE "-20/-10°C" ÷ "-24/-12°C"
key: the LED
will flash
key within 15 s; see also r1 and r2 parameters
key or do not operate for 15 s: the LED
U.M.
WORKING SETPOINT
°C/°F (1)
working setpoint; see also r0 and r12
key for 4 s: the display will show "PA"
key within 15 s to set the value determined with the "PAS" parameter (the parameter is set at "-19" by
or do not operate for 15 s: the display will show "SP"
(1 = YES)
will switch off after which, the device will exit the procedure.
18