- defrost will be requested but a compressor minimum switch-on shall be in progress
Evaporator fan LED
If the LED is on the evaporator fan will be on
If the LED is flashing evaporator fan standstill will be in progress
Auxiliary LED
If the LED is on:
- the room light will be on in manual mode
- the demister heating elements will be on
- the auxiliary output will have been turned on in manual mode
- the alarm output will be active
- the door heating elements will be on
AUX
- the neutral area operation heating elements will be on
- the condenser fan will be on
- the on/stand-by output shall be active
If the LED is flashing:
- the room light will be on by door switch input
- the auxiliary output will have been turned on from the multifunction input
- the condenser fan will be delayed in turning off
Energy saving LED
If the LED is on and the display is switched on, the "energy saving" function is in progress
If the LED is on and the display is switched off, the "low consumption" function is in progress; touch a key to restore
normal display
Maintenance LED
if it is on, the compressor must be maintained
Celsius degrees LED
°C
If the LED is on, the unit of measurement for temperature is Celsius degrees
If it is flashing, the "rapid cooling" or "rapid heating" function will be in progress
Fahrenheit degrees LED
°F
If the LED is on, the unit of measurement for temperature Is Fahrenheit degrees
If it is flashing, the "rapid cooling" or "rapid heating" function will be in progress
LED on/stand-by
If the LED is on, the device is switched off ("standby" status)
CODE
MEANING
Loc
the keyboard is blocked
- - -
the operation requested is not available
dEF
defrost is in progress
CODE
MEANING
Minimum temperature alarm
Solutions:
AL
- check the room temperature or CPT temperature; see A1 parameter
Main consequences:
- the alarm output will be switched on
Maximum temperature alarm
Solutions:
AH
- check the room temperature or CPT temperature; see A4 parameter
Main consequences:
- the alarm output will be switched on
Door switch input alarm
Solutions:
- check the causes of the activation of the input; see i0 and i1 parameters
id
Main consequences:
- the effect established with the i0 parameter
- the alarm output will be switched on
Multifunction input alarm
Solutions:
- check the causes of the activation of the input; see i5 and i6 parameters
iA
Main consequences:
- the effect established with the i5 parameter
- the alarm output will be switched on
Condenser overheated alarm
Solutions:
- check the condenser temperature; see C6 parameter
COH
Main consequences:
- the alarm output will be switched on
- the condenser fan will be switched on
Signals
Alarms
27