Energy saving LED
If the LED is on and the display is switched on, the "energy saving" function is in progress
If the LED is on and the display is switched off, the "low consumption" function is in progress; touch a key to restore
normal display
Celsius degrees LED
°C
If the LED is on, the unit of measurement for temperature is Celsius degrees
Fahrenheit degrees LED
°F
If the LED is on, the unit of measurement for temperature is Fahrenheit degrees
LED on/stand-by
If the LED is on, the device is switched off
CODE
MEANING
Loc
the keyboard is blocked
- - -
the operation requested is not available
dEF
defrost is in progress
CODE
MEANING
Minimum temperature alarm
Solutions:
AL
- check the room temperature; see A1 parameter
Main consequences:
- the device will continue to operate normally
Maximum temperature alarm
Solutions:
AH
- check the room temperature; see A4 parameter
Main consequences:
- the device will continue to operate normally
Door switch input alarm
Solutions:
id
- check the causes of the activation of the input; see i0 and i1 parameters
Main consequences:
- the effect established with the i0 parameter
Multifunction input alarm or pressure switch alarm
Solutions:
iA
- check the causes of the activation of the input; see i0 and i1 parameters
Main consequences:
- the effect established with the i0 parameter
Condenser overheated alarm
Solutions:
COH
- check the condenser temperature; see C6 parameter
Main consequences:
- the device will continue to operate normally
Compressor shut down alarm
Solutions:
- check the condenser temperature; see C7 parameter
- switch the device off and back on again: if when the device is switched back on, the temperature
CSd
of the condenser is still higher than that established in C7 parameter, disconnect the power supply and clean the
condenser
Main consequences:
- the compressor will be switched off
Defrost alarm switched off because maximum time has been reached
Solutions:
- check the integrity of the evaporator probe; see d2, d3 and d11 parameters
dFd
- touch a key to restore normal display
Main consequences:
- the device will continue to operate normally
When the cause of the alarm disappears, the device restores normal operation, except for the following alarms:
- compressor shut down alarm (code "CSd") which requires the switching off of the device or the temporary suspension of the power
supply.
- defrost alarm switched off because maximum time has been reached (code "dFd") which requires the touching of a key
CODE
MEANING
Room temperature probe error
Pr1
Solutions:
Signals
Alarms
Errors
24