Refer to Tables 5-2&5-3 for the specifications of the power cord and communication wire. A wiring capacity that is too small will
cause the electrical wiring to become too hot, and lead to accidents when the unit burns and becomes damaged.
Select the wire diameters( minimum value) individually for each unit based on the table 5-3.
Maximum allowable voltage range variation between phases is 2%.
Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection,where MFA is
used to select the current circuit breakers and residual current operation breakers:
Model
Power
supply
Communication wire between
indoor unit and wired controller *
CIRCUIT BREAKER/FUSE(A)
Please refer to the corresponding wired controller manual for the wired
controller wiring.
Rated current of appliance(A)
≤3
>3
and
≤6
>6
and
≤10
>10
and
≤16
>16
and
≤25
>25
and
≤32
>32
and
≤50
>50
and
≤63
Iron plastic strip
Figure 5-21 Cabling diagram(DC FAN)
Table 5-2
Phase
Volt and frequency
Shielded
Table 5-3
Nominal cross-sectional area (mm )
Flexible cords
0.5 and
0.75
and
1
and
1.5
and
2.5
and
4
and
6
and
10
and
15
Cable
ALL
1-phase
220-240V~50/60Hz
×AWG16-AWG18
15/15
2
Cable for fixed wiring
0.75
1
1
1
1
1.5
1.5
2.5
2.5
4
4
6
10
6
16
10
Positioning
thread buckle
and
2.5
and
2.5
and
2.5
and
4
and
6
and
10
and
16
and
25