6.0 ELECTRICAL RATINGS
For versions which are equipped with a microswitch only, the maximum values for each switch fitted are
specified in the table below:
For versions which are equipped with the encapsulated housing, see the values stated on the
certification label for reference.
7.0 SPECIAL CONDITIONS
1.
The units must be incorporated in systems which limit the electrical supply ratings to the values
above
2.
The wiring loom between the fixed and detatchable enclosure shells must be located, during
assembly, such that the conductors and the restraint loop are not trapped in the sealing face
between shells
3.
The encapsulated resistor/diode units shall be protected by fuses rated for a prospective short
circuit current of at least 1500A
4.
The cable glands of the unit are to be provided with sealing washers to maintain the IP66/IP67
rating of the enclosure.
11/17
Voltage (d.c.)
Resistive load (A)
30
50
75
0.75
125
250
0.25
Voltage (a.c.)
Resistive load (A)
125
250
Inductive load (A)
5
3
1
1
0.75
0.5
0.03
0.03
Inductive load (A)
5
5
5
5
© Eaton MEDC Ltd 2017