Error messages
On devices with the X-Series Premium Controller, error numbers are shown on the LCD display. With the
ECoolPLANT software it is possible to read the error numbers on the computer.
 The blinking of the red LED light on the controller circuit board is not a fault indicator or error message. The red
LED light indicates that voltage is supplied to the cooling unit.
Error
Fault
no.
• LED:
Er00
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
• LED:
Er01
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
• LED:
Er04
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
• LED:
Er05
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• External heating:
• Fault signal contact:
Operating Manual DTS and DTI 6X2E Premium Controller X-Series (XC) 086100099e © Pfannenberg GmbH
Unit activity
Possible causes
• Door contact:
Blinking
• The door contact loop has
0%
been interrupted.
0%
0%
0%
Closed
• Pressostat tripped:
Blinking
• Excessively high pressure
0%
has built up in the
100%
refrigerant circuit. The
cooling unit cannot
100%
dissipate the heat from the
0%
refrigerant circuit.
Open
• Phase sequence / phase
Blinking
0%
loss:
• Failure of at least one
0%
phase or the phase
sequence is incorrect
0%
(only with alternating
0%
current units with rotating
Open
piston compressors).
• Sensor 1 (TS1) defect.
Blinking
• Cooling unit switches to
100%
forced cooling.
100%
100%
0%
Open
Corrective measures
▪ Close door.
▪ Connect door contact
switch.
▪ Bypass door contact.
▪ Check wiring.
▪ Allow the unit to cool
down.
▪ Clean the heat
exchanger fins
(internal/external).
▪ Check condenser fan
(external) for function.
▪ Check the field of
rotation - (clockwise
rotation is required).
▪ All phases must carry
rated voltage.
▪ Replace Sensor 1 or the
controller circuit board
according to the unit
type.
▪ Replace controller circuit
board if the sensor is
soldered in place.
Page 29 / 41