Table 6-2 Outdoor unit error codes
Nº
Code
1
E1
Communication malfunction beetwen indoor and outdoor units
2
F0
Current overload protection
3
F1
Outdoor room temperature sensor (T4) open circuit or short circuit
4
F2
Outdoor coil temperature sensor (T3) open circuit or short circuit
5
F3
Outdoor discharge temperature sensor (T5) open circuit or short circuit
6
F4
Outdoor EEPROM error
7
F5
Outdoor fan speed malfunction
8
P0
Inverter module IPM protection
9
P1
High/Low voltage protection
10
P3
Outdoor low temperature protection
11
P4
Rotor position protection of compressor
12
P7
Sensor of outdoor IGBT is faulty
13
J0
High temperature position of indoor heat exchanger in heating mode
14
J1
High temperature position of indoor heat exchanger in cooling mode
15
J2
High discharge temperature protection
16
J3
PFC module protection
17
J4
Communication error between outdoor main chip and compressor driven chip IR341
18
J5
High pressure protection
19
J6
Low pressure protection
20
J8
AC voltage protection
In low ambient cooling mode, the LED displays"LC" or alternative displays between running frequency and "LC"
(each displays 0.5s)
Table 6-3
Symptoms
Unit does not start
Air flowing normally but
completely can't cooling
Units start or stop frequently
Low cooling effect
Low heating effect
Description
Causes
Power failure.
Power switch is off.
Fuse of power switch may have burned.
Batteries of remote controller exhausted
or other problem of controller.
Temperature is not set correctly.
Be
in
3
minutes
protection
compressor.
Refrigerant is too little or too much.
Air or no concretingc gas in the
refrigerating circuit.
Compressor is malfunction.
Voltage is too high or too low.
System circuit is blocked.
Outdoor unit and indoor unit heat
exchanger is dirty.
The air filter is dirty.
Inlet/outlet of indoor/outdoor units is
blocked.
Doors and windows are open
Sunlight directly shine.
Too much heat resource.
Outdoor temp. is too high.
Leakage of refrigerant or lack of
refrigerant.
Outdoor temperature is lower than 7 C
Doors and windows not completely
closed.
Leakage of refrigerant or
refrigerant.
63
Solution
Wait for the comeback of power.
Switch on the power.
ReplLocation:
Replace the batterises or check the
controller.
Set the temperature properly.
of
Wait.
Check leakage, and rightly recharge
refrigerant.
Vacuum and recharge refrigerant.
Maintenance or change compressor.
Install manostat.
Find reasons and solution.
Clean the heat exchanger.
Clean the air filter.
Eliminate all dirties and make air
smooth.
Close doors and windows.
Make curtains in order to shelter from
sunshine.
Reduce heat source.
AC cooling capacity reduces (normal).
Check leakage and rightly recharge
refrigerant.
Use heating device.
Close doors and windows.
Check leakage and rightly recharge
lack of
refrigerant.