V/W2 – This terminal is used to connect the modulating
signal (V) from a non-communicating, fully modulating
thermostat specified for use with this furnace. It is used
to transmit the firing rate (determined by the thermostat)
to the furnace control.
NOTE: Do not apply 24 VAC to the V/W2 terminal (as
with a jumper to R for diagnostic purposes) with a
non-communicating, modulating thermostat.
B - This terminal is used to pass a reversing valve
signal to a condenser. It is only a holding place for
connecting a wire from the thermostat and a wire from the
condenser. It does not change the airflow of the cool/heat
commands.
Figure 14 – Wiring Diagram Modulating t-stat
Unit size
Volts-Hertz-Phase
15,000
30,000
45,000
60,000
75,000
105,000
120,000
Heating
system
Modulating
chinook
Modulating
chinook
Modulating
1&2 stage Non-Alizé
chinook
Cooling unit/Heat pump
Table 10 – Electrical Data
Operating
range Min
120-60-1
127
120-60-1
127
120-60-1
127
120-60-1
127
120-60-1
127
120-60-1
127
120-60-1
127
Table 11 – Thermostat Choice VS System
Cooling
Thermostat
system
Alizé
R02P032
1 stage Non-Alizé
Cooling unit
R02P032
R02P032
6.4
ALTERNATE POWER SUPPLY
Dettson doesn't recommend to operate the furnace on a
generator or other alternate power supply. If so it must
produce a smooth sinusoidal waveform for compatibility
with the furnace electronics. The alternate power supply
must generate the same voltage, phase, and frequency
(Hz) as shown on the furnace rating plate.
Power from an alternate power supply that is non-
sinusoidal may damage the furnace electronics or cause
erratic operation.
Contact the alternate power supply manufacturer for
specifications and details.
Operating
Maximum
range Max
unit amp
104
10.7
104
10.7
104
10.7
104
13.1
104
13.1
104
15.8
104
15.8
HRV interlock
at low CFM
Yes
Yes
2-Stage
No
17
Unit
Maximum fuse
ampacity
CKT BRK amp
12.6
15
12.6
15
12.6
15
15.6
20
15.6
20
19
20
19
20
Interface
Smart Duct
board needed
compliant
Yes
Yes
Yes
No
No
No