Diagramme 1 : Remote-signal
H
L
Un signal bas d'une longueur indéterminée déclenche le signal Remote
1.) signal haut de 30 ms – 120 ms
2.) signal bas de 30 ms – 120 ms
3.) signal haut de 200 ms – 400 ms
4.) signal bas de 200 ms – 400 ms
5.) signal haut de 200 ms – 400 ms
6.) signal bas de 30 ms – 120 ms
7.) signal haut de max. 256 s
Le signal Remote est traité sur le dernier front descendant et l'horloge est déclenchée.
Prescriptions :
ATEX
II 3G Ex nA nC IIC T3 Gc
Harzardous Areas: An enclosure / cabinet rated min. IP54 must be provided in the final installation.
The enclosure / cabinet must be in accordance with the requirement of EN 60079-0:2009 and/or EN60079-15:2010
DIP switches shall not be used in operation or while a hazardous area may be present
RS 232 must be fixed with screws as intended
The USB-interface cable has to be secured according to the requirements of EN 60079-15:2010, otherwise a permanent connection /
disconnection or operation is not permitted while hazardous area conditions may be present.
Without meeting the requirements of EN 60079-15:2010, the USB-cable is permitted for installation / maintenance only.
ATTENTION
SEPARATION DES CONNECTIONS UNIQUEMENT EN ATMOSPHERES NON-EXPLOSIBLES !
UTILISER LES COMMUTATEURS UNIQUEMENT EN ZONES NON EXPLOSIBLES !
Le connecteur de signaux utilisé en atmosphère explosible doit être pourvu de fixations supplémentaires afin de répondre à EN 60079-15.
Montage = Montage
Anleitung Montage / Demontage = Instructions de montage / démontage
Demontage = Démontage
© Siemens AG 2016
A5E38473417, 08.2016
1
2
3
4
© Siemens AG Österreich, AT-1210 Vienna, Austria. All rights reserved.
Sous réserve de modifications techniques et de disponibilité de livraison.
6 sur 6
5
6
7
SITOP DC-USV-Modul 15
t