CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the
battery. Service the battery under the supervision of personnel knowledgeable of
batteries and their precautions.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in
a fire, as they may explode. Follow all local ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin
and eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take
the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source
of ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL
SHOCK! The likelihood of such shock will be reduced if such grounds are removed during
installation and maintenance (applicable to a UPS and a remote battery supply not having a
grounded circuit)
BATTERY REPLACEMENT PROCEDURE:
1. Remove the right-side of the faceplate.
4. Remove the retaining screw of the cable
connectors.
REMINDER: Batteries are consider HAZARDOUS WASTE and must be disposed of properly. Almost any
retailer that sells lead-acid batteries collects used batteries for recycling, as required by most state laws.
BATTERY REPLACEMENT
2. Remove the three retaining screws on the
cable protection cover then remove the cover
faceplate.
5. Replace the new battery pack. Assemble the screws, cover,
cable and front panel in the reverse sequence of above steps.
Recharge the unit for 4-8 hours to ensure the UPS performs
expected runtime.
3. Disconnect the black and red cables.