Télécharger Imprimer la page

Mitsubishi Electric CITY MULTI TPLFYP EM140 Serie Mode D'emploi page 16

Climatiseurs pour bâtiments, unité intérieure
Masquer les pouces Voir aussi pour CITY MULTI TPLFYP EM140 Serie:

Publicité

Les langues disponibles

Les langues disponibles

7. Test run
Step 1 Switch the remote controller to "Test run".
1 Select "Service" from the Main menu, and press the [SELECT/HOLD] button.
2 When the Service menu is selected, a window will appear asking for the password. (Fig. 7-2)
To enter the current maintenance password (4 numerical digits), move the cursor to the digit you want to change with the
(0 through 9) with the
F3
Note: The initial maintenance password is "9999". Change the default password as necessary to prevent unauthorized access.
Have the password available for those who need it.
Note: If you forget your maintenance password, you can initialize the password to the default password "9999" by pressing and holding the
simultaneously for three seconds on the maintenance password setting screen.
3 Select "Test run" with the
F1
4 Select "Test run" with the
F1
Service menu
Enter maintenance password
Select: SELECT
Cursor
RETURN SELECT
MENU
HOLD
Fig. 7-2
Step 2 Perform the test run and check the airflow temperature and auto vane.
1 Press the
button to go through the operation modes in the order of "Cool"
F1
and "Heat". (Fig. 7-5)
Cool mode: Check the cold air blow off.
Heat mode: Check the heat blow off.
Note:
Check the operation of the outdoor unit's fan.
2 Press the [SELECT/HOLD] button and open the Vane setting screen.
AUTO vane check
1 Check the auto vane with the
2 Press the [RETURN] button to return to "Test run operation".
3 Press the [ON/OFF] button.
Backlit LCD
TEMP.
button
MODE
button
en
15
or
F4
button. Then, press the [SELECT/HOLD] button.
or
F2
button, and press the [SELECT/HOLD] button. (Fig. 7-3)
or
F2
button, and press the [SELECT/HOLD] button. (Fig. 7-4)
Service menu
Test run
Input maintenace info.
Settings
Check
Others
Main menu: RETURN
Cursor
ON
RETURN SELECT
MENU
OFF
Fig. 7-3
F1 F2
buttons. (Fig. 7-6)
ON/OFF lamp
The lamp will light up in green
when turned on, and blink during
startup and when an error occurs.
button
ON/OFF
Pressing this button starts and
stops the operation.
.
FAN
button
VANE
button
Fig. 7-7
Test run menu
Test run
Drain pump test run
Service menu: MENU
Cursor
ON
MENU
OFF
HOLD
Test run
Pipe
Cool
Switch disp.
SELECT
Mode
RETURN SELECT
MENU
Fig. 7-5
7.2.2. Test run
Using Simple MA remote controller (Fig. 7-7)
Before making a test run, refer to the "Test Run" section of the indoor unit instal-
1
lation manual.
When the [ON/OFF] button and [TEMP.
2
2 seconds or longer, test run is performed.
Stop the test run by pressing the [ON/OFF] button.
3
If an error code is displayed on the remote controller or if the air conditioner does
4
not operate properly, refer to the outdoor unit installation manual or other technical
materials.
Indoor unit piping temperature
Display range: -4ºF (-20ºC) to 158ºF
(70ºC)
"-4ºF" or "158ºF" flashes on the
display.
or
F2
button, and set each number
F1
ON
RETURN SELECT
OFF
HOLD
Fig. 7-4
Remain
Test run
Auto
Fan
ON
MENU
OFF
HOLD
] button are pressed simultaneously for
The remaining time for test run
is displayed.
Display range: 2:00 to 0:01
After two hours, the test run
stops automatically.
COOL
VENTI.
and
buttons
F1
F2
Remain
Vane
ON
RETURN SELECT
OFF
HOLD
Fig. 7-6
Test run time

Publicité

loading

Ce manuel est également adapté pour:

City multi tplfyp em141 serie