Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Commissioning, operation
Menu
Description
item
Reset delay time, which must occur without
DR1 /
DR2
interruption before any electrical signal change occurs
(RP1, if applicable RP2)
OU1 /
Switching function (switching output 1/if applicable 2)
OU2
OU3
Setting of analouge output signal
POL1 /
Switching logic (switching output 1/if applicable 2)
POL2
SEL2 /
Selection for measuring signal of output 2 and, if
SEL3
applicable, of output 3
ALOW
Measuring range scaling/turndown (analogue value,
start value)
AHGH
Measuring range scaling/turndown (analogue value,
end value)
AVGD
Dampening (digital display)
Display value in display mode
DISM
DISR
Rotate the indication by 180° (digital display)
RHL
Clear memory (min/max flow)
PAS
Password entry
TAG
Measuring instrument name (TAG)
WIKA operating instructions flow switch, model FSD-4
Parameter
0.00 ... 65.00 s
HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
I = 4 ... 20 mA
U = DC 0 ... 10 V
PNP, NPN
FLOW / TEMP
Corresponding to analogue output
Corresponding to analogue output
0.00 ... 65.00 s
ACT = Current flow value
HIGH/LOW = MAX/MIN flow
ACTT = Current temperature
OFF = display off
YES/NO
YES/NO
0000 = no password
Password input digit by digit
32 selectable characters (A-Z ‚0 ... 9; - ‚SPACE)
(2 spaces in sequence terminate the input and
lead to the deletion of this and the underlying
characters)
Factory
setting
0.00 s
EN
HNO
I
PNP
FLOW
Start of
measuring
range
End of
measuring
range
0.20 s
ACT
No
-
0000
Without
17

Publicité

Table des Matières
loading

Table des Matières