Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Commissioning, operation
POL2
SEL2
SEL3
ALOW
AHGH
AVGD
DISM
DISR
RHL
PAS
TAG
END
END

5.6 Adjustment

Should you wish to adjust the flow switch to local flow conditions, the FSD-4 offers two ways to make this adjustment.
5.6.1 Adjustment for all units except %
1. Depressurise the system and switch off the flow.
2. Mount the flow switch and connect it electrically.
→ see chapter 5.1 "Mechanical mounting" and 5.2 "Electrical mounting"
3. Select required flow unit in the "INI" menu under "UNIF".
4. If there is no flow, select the menu item "0SET" in the "INI" menu, select "YES" and confirm.
5. Set the flow to a known value in the plant.
6. Compare this value with the display and calculate the multiplier for the flow value.
Example: System flow velocity: 2.3 m/s
Display FSD-4: 2.5 m/s
muF = 2.3 / 2.5 = 0.92
WIKA operating instructions flow switch, model FSD-4
Para
Only visible when 2nd switching output is available
Para
Only visible when 2nd switching output is available
Para
Only visible when analogue output is available
Value
Only visible when analogue output is available
Value
Only visible when analogue output is available
Value
Para
YES/NO
YES/NO
Value
Value
EN
19

Publicité

Table des Matières
loading

Table des Matières