3) Manual manoeuvre from inside or release
!
The manual manoeuvre must be made exclusively with
the door stopped and after disconnecting power from the
electrical control unit.
4) Testing
The whole system must be tested by qualified and expert staff who
must perform the tests required, according to the level of risk.
To test SPIDO, proceed as follows:
• close the door;
• disconnect the power supply;
• release the gear motor;
• check that the slide way is clean and free from debris;
• completely open the door manually making sure to always exercise
a force of less than 150N (15kg);
• check that the door does not stick when moving;
• check that when the door is stopped at any point and released it
remains motionless;
5) Maintenance
SPIDO does not require any special maintenance during its lifetime,
but a scheduled control at least every 6 months will not only ensure
that the gear motor lasts longer but also that the system works
correctly and safely.
5.1) Disposal
SPIDO comprises various types of materials which must be disposed
of in compliance with the laws of the country of installation.
6) Technical specifications
Power input
Line absorption
Max. absorbed power
Speed
Travel Y
Max. thrust
Max. traction
Operating temperature
Work cycles
Weight of motor (with profile)
Protection level
4
All manuals and user guides at all-guides.com
1. Pull the knob downwards and push the door (Fig. 14);
2. Turn the handle and push the door (Fig. 15).
• check that the safety systems are in good condition;
• check that the screw connections are perfectly tight;
• check the chain is taut and that it slides well, lubricate if necessary;
• after carrying out the above checks, block the gear motor and
• adjust (from the electronic control unit) current sensitivity so that it
• measure the force of impact as required by EN12445 and
Maintenance may only be performed by qualified staff.
Maintenance involves repeating the test procedure.
There are no particular dangers or risks deriving from demolition of the
system. If waste sorting is required, the components should be
grouped by type of material (electrical, aluminium, plastic, etc.).
SP6000 230V ~
(Vac)
230
(A)
0,65
(W)
(m/s)
(mm)
(N)
(N)
(°C)
(%)
(kg)
(IP)
power the control unit.
can move just the door;
EN12453 standards.
150
0,15
2500
650
700
-20 ÷ +50
30
12
40
SP6000 110V ~
110
1,3